Zone1 Extension Scheme; Figure 113: Zone 1 Extension Scheme; Figure 114: Zone 1 Extension Logic - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
5

ZONE1 EXTENSION SCHEME

Auto-reclosure is widely used on radial overhead line circuits to re-establish supply following a transient fault. A
Zone 1 extension scheme may be applied to a radial overhead feeder to provide high speed protection for
transient faults along the whole of the protected line. The figure below shows the alternative reach selections for
zone 1: Z1 or the extended reach Z1X.
A
Z1 Extension (B)
E02739

Figure 113: Zone 1 extension scheme

In this scheme Zone 1X is enabled and set to overreach the protected line. A fault on the line, including one in the
end 20% not covered by Zone 1, results in instantaneous tripping followed by autoreclosure. Zone 1X has resistive
reaches and residual compensation similar to Zone 1. The autorecloser is used to inhibit tripping from Zone 1X so
that on reclosure the device operates with Basic scheme logic only, to co-ordinate with downstream protection for
permanent faults. Therefore transient faults on the line are cleared instantaneously, which reduces the probability
of a transient fault becoming permanent. However, the scheme can operate for some faults on an adjacent line,
although this is followed by autoreclosure with correct protection discrimination. Increased circuit breaker
operations would occur, together with transient loss of supply to a substation.
First fault trip
Fault trip for persistent fault on auto-reclose
The Zone 1 extension scheme can be disabled, permanently enabled or just brought into service when the
communication channel fails and the aided scheme is inoperative. If used in conjunction with a channel-aided
scheme, Z1X can be set to be enabled when Ch1 or Ch2 fails, or when all channels fail, or when any channel fails.
Reset Zone 1 Ext
Z1 Ext Scheme
Enabled
En. on Ch 1 Fail
En. on Ch 2 Fail
En. All Ch Fail
En. Any Ch Fail
Aid 1 Chan Fail
Aid 2 Chan Fail

Figure 114: Zone 1 extension logic

P446SV-TM-EN-1
Z1A
Fault trip
490
317
1
318
Z1 Extension (A)
ZL
= tZ1
= tZ2
&
1
&
&
&
&
Chapter 9 - Non-Aided Schemes
B
Z1X time delay
876
Z1 X Active
V02754
221