Chapter 21 - Communications
The switch IP address must be configured through the Ethernet network.
Set by Switch Manager for SHP and DHP
Set by RSTP Configurator for RSTP
Set by PRP/HSR Configurator for PRP or HSR
V01018

Figure 278: IED and REB IP address configuration

5.7.1

CONFIGURING THE IED IP ADDRESS

If you are using IEC 61850, set the IED IP address using the IEC 61850 Configurator software. In the IEC 61850
Configurator, set Media to Single Copper or Redundant Fibre.
If you are using DNP3 over Ethernet, set the IED IP address by editing the DNP3 file, using the DNP3 Configurator
software. In the DNP3 Configurator, set Ethernet Media to Copper, even though the redundant Ethernet network
uses fibre optic cables.
5.7.2

CONFIGURING THE REB IP ADDRESS

The board IP address must be configured before connecting the IED to the network to avoid an IP address conflict.
The way you configure the IP address depends on the redundancy protocol you have chosen.
PRP/HSR
If using PRP or HSR, you configure the REB IP address using the PRP/HSR Configurator software.
RSTP
If using RSTP, you configure the REB IP address using the PRP/HSR Configurator software.
SHP or DHP
If using SHP or DHP the first two octets are set by the Switch Manager software or an SNMP MIB browser. The third
octet is fixed at 254 (FE hex, 11111110 binary), and the fourth octet is set by the on-board dip switch.
Note:
An H35 (SHP) or H36 (DHP) network device is needed in the network to configure the REB IP address if you are using SNMP.
5.7.2.1
CONFIGURING THE LAST OCTET (SHP, DHP, RSTP)
If using SHP or DHP, the last octet is configured using board address switch SW2 on the board. Remove the IED
front cover to gain access to the board address switch.
Warning:
Configure the hardware settings before the device is installed.
1.
Refer to the safety section of the IED.
2.
Switch off the IED. Disconnect the power and all connections.
520
Set by IED Configurator
IED (IP1)
AAA.BBB.CCC.DDD
REB (IP2)
WWW.XXX.YYY.ZZZ
Set by Hardware Dip Switch SW2 for SHP, DHP, or RSTP
Set by PRP/HSR Configurator for PRP or HSR
Fixed at 254 for SHP or DHP
Set by PRP/HSR/RSTP Configurator for PRP, HSR or RSTP
P446SV
P446SV-TM-EN-1