Maximum permitted phase angle between Line and Bus 1 voltages for second stage synchronism check element to reclose CB1
CB1 CS2 VDiff
Check Synch Voltage differential setting decides that stage 2 System Check Synchronism logic for CB1 is blocked if Vdiff> is one of the
selected options in setting CB1 CS Volt.Blk (48 8 E), and voltage magnitude difference between line and bus 1 voltage is above this setting.
CB1 CS2 SlipCtrl
Setting to enable or disable blocking of synchronism check stage 2 for reclosing CB1 by excessive frequency difference (slip) between line
and bus voltages (refer to setting CB1 CS2 SlipFreq)
CB1 CS2 SlipFreq
If CB1 CS2 SlipCtrl is enabled, synchronism check stage 2 is blocked for reclosing CB1 if measured frequency difference between line and bus
voltages is greater than this setting.
CB1 CS2 Adaptive
Setting to enable or disable Adaptive CB closing with System Check Synchronism stage 2 closing for CB1: logic uses set CB1 CI Time to issue
CB1 close command at such a time that the predicted phase angle difference when CB1 main contacts touch is as close as possible to 0
degrees. If Adaptive closing is disabled, the logic issues CB1 close command as soon as phase angle comes within set limit at CB1 CS2 Angle
.
CB1 Cl Time
This sets CB1 closing time, from receipt of CB1 close command until main contacts touch.
Sys Checks CB2
Setting to enable or disable both stages of system checks for reclosing CB2.
If Sys Checks CB2 is set to Disabled, all other menu settings associated with synchronism checks for CB2 become invisible, and a DDB (1484)
signal SChksInactiveCB2 is set.
CB2 CS Volt. Blk
Setting to determine which, if any, conditions should block synchronism check for CB2 (undervoltage V<, overvoltage V>, and/or voltage
differential Vdiff etc) for the line and bus voltages.
CB2 CS1 Status
Setting to enable or disable the stage 1 synchronism check elements for auto-reclosing and manual closing CB2.
CB2 CS1 Angle
Maximum permitted phase angle between Line and Bus 2 voltages for first stage synchronism check element to reclose CB2.
CB2 CS1 VDiff
Check Synch Voltage differential setting decides that stage 1 System Check Synchronism logic for CB2 is blocked if Vdiff> is one of the
selected options in setting CB2 CS Volt. Blk (48 9C), and voltage magnitude difference between line and bus 2 voltage is above this setting.
CB2 CS1 SlipCtrl
Setting to enable or disable blocking of synchronism check stage 1 for reclosing CB2 by excessive frequency difference (slip) between line
and bus voltages (refer to setting CB2 CS1 SlipFreq).
CB2 CS1 SlipFreq
If CB2 CS1 SlipCtrl is enabled, synchronism check stage 1 is blocked for reclosing CB2 if measured frequency difference between line and bus
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
48
96
6.5
48
97
Enabled
48
98
0.05
48
99
Disabled
48
9A
0.05
48
9B
Disabled
48
9C
V<
48
9D
Enabled
48
9E
20
48
9F
6.5
48
A0
Enabled
48
A1
0.05
DESCRIPTION
[Courier Number (angle)]
From 1 to 120 in steps of 0.5
[Courier Number (voltage)]
Disabled
Enabled
[Indexed String]
From 0.005 to 2 in steps of 0.005
[Courier Number (frequency)]
Disabled
Enabled
[Indexed String]
From 0.01 to 0.5 in steps of 0.001
[Courier Number (time-seconds)]
Disabled
Enabled
[Indexed String]
None
V<
V>
Vdiff>
V< and V>
V< and Vdiff>
V> and Vdiff>
V< V> and Vdiff>
[Indexed String]
Disabled
Enabled
[Indexed String]
From 0 to 90 in steps of 1
[Courier Number (angle)]
From 1 to 120 in steps of 0.5
[Courier Number (voltage)]
Disabled
Enabled
[Indexed String]
From 0.005 to 2 in steps of 0.005
[Courier Number (frequency)]