Appendix B -Settings and Signals
ORDINAL
831
VC< start
Phase C undervoltage level detector used in the pole dead logic. Detectors have a fixed threshold: undervoltage pickup 38.1 V-drop
off 43.8 V
832
VTS Fast Block
VT supervision fast block - blocks elements which would otherwise maloperate immediately a fuse failure event occurs
833
VTS Slow Block
VT supervision slow block - blocks elements which would otherwise maloperate some time after a fuse failure event occurs
834
CB1 Fail1 Trip
Bfail1 Trip 3ph
835
CB1 Fail2 Trip
Bfail2 Trip 3ph
836
CB2 Fail1 Trip
tBF1 trip 3Ph - three phase output from circuit breaker failure 2 logic, stage 1
837
CB2 Fail2 Trip
tBF2 trip 3Ph - three phase output from circuit breaker failure 2 logic, stage 2
838
Control TripCB1
Control trip - operator trip instruction to circuit breaker 1, via menu, or SCADA. (Does not operate for protection element trips)
839
Control CloseCB1
Control close command to circuit breaker 1. Operates for a manual close command (menu, SCADA), and additionally is driven by the
auto-reclose close command
840
Control TripCB2
Control trip - operator trip instruction to circuit breaker 2, via menu, or SCADA. (Does not operate for protection element trips)
841
Control CloseCB2
Control close command to circuit breaker 2. Operates for a manual close command (menu, SCADA), and additionally is driven by the
auto-reclose close command
842
CB1 Close inProg
Control Close in Progress
843
Block Main Prot
AR Block Main Protection. In P841 etc, there is no specific output DDB to block selected protection functions. If such a feature is
required for a particular application, appropriate mapping should be created in PSL, using output DDBs from sequence counter,
single phase dead time and three phase dead time logic as required.
844
CB1 AR 3p InProg
CB1 Auto Reclose/(AR 3 pole) in Progress
845
CB1 AR 1p InProg
CB1 AR 1pole in progress
846
Seq Counter = 0
Auto-reclose sequence counter is at zero - no previous faults have been cleared within recent history. The sequence count is at zero
because no reclaim times are timing out, and the auto-recloser is not locked out. The recloser is awaiting the first protection trip, and
all programmed cycles are free to follow
847
Seq Counter = 1
The first fault trip has happened in a new auto-reclose sequence. Dead time 1, or reclaim time 1 are in the process of timing out
848
Seq Counter = 2
Auto-reclose sequence counter is at 2. This means that the initial fault trip happened, and then another trip followed, moving the
counter on to 2
849
Seq Counter = 3
Auto-reclose sequence counter is at 3. This means that the initial fault trip happened, and then 2 trips followed, moving the counter
on to 3
850
Seq Counter = 4
Auto-reclose sequence counter is at 4. This means that the initial fault trip happened, and then 3 trips followed, moving the counter
on to 4
851
Seq Counter = 5
Seq Counter = 5 (In 2CB AR, there is no output specifically for seq counter = 5. However there is a DDB output for Seq Counter > 4.
may need a different allocation for DDB#851 in 2CB AR scheme.
852
CB1 Succ 3P AR
This signal is set when CB1 has successfully completed a three phase autoreclose cycle.
853
3P Dead Time IP
2CB logic provides separate output DDBs indicating (i) single phase dead time in progress, (ii) three phase dead time in progress (all
shots), (iii) 3 ph 1st shot dead time in progress, (iv) 3 ph 2nd shot dead time in progress, (v) 3 ph 3rd shot dead time in progress, (vi) 3 ph
4th shot dead time in progress.
B176
SIGNAL NAME
DDB_PHASE_C_UNDERVOLTAGE
DDB_VTS_FAST_BLOCK
DDB_VTS_SLOW_BLOCK
DDB_CBF1_TRIP_3PH
DDB_CBF2_TRIP_3PH
DDB_CB2F1_TRIP_3PH
DDB_CB2F2_TRIP_3PH
DDB_CONTROL_TRIP
DDB_CONTROL_CLOSE
DDB_CONTROL_TRIP_2
DDB_CONTROL_CLOSE_2
DDB_CONTROL_CLOSE_IN_PROGRESS
DDB_AR_BLOCK_MAIN_PROTECTION
DDB_AR_3_POLE_IN_PROGRESS
DDB_AR_1_POLE_IN_PROGRESS
DDB_SEQ_COUNT_0
DDB_SEQ_COUNT_1
DDB_SEQ_COUNT_2
DDB_SEQ_COUNT_3
DDB_SEQ_COUNT_4
DDB_SEQ_COUNT_5
DDB_AR_SUCCESSFUL_RECLOSE
DDB_DEAD_TIME_IN_PROGRESS
ELEMENT NAME
DESCRIPTION