GE MiCOM P40 Technical Manual page 911

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
ORDINAL
439
Init Trip CB1
Initiate tripping of circuit breaker 1 from a manual command
440
Init Close CB1
Initiate closing of circuit breaker 1 from a manual command
441
Init Trip CB2
Initiate tripping of circuit breaker 2 from a manual command
442
Init Close CB2
Initiate closing of circuit breaker 2 from a manual command
443
Rst CB1 CloseDly
Reset Manual CB Close Timer Delay (stop & reset Manual Close Delay time for closing CB1).
444
Reset Relays/LED
Reset latched relays & LEDs (manual reset of any lockout trip contacts, auto-reclose lockout, and LEDs)
445
Reset Thermal
Reset thermal state to 0%
446
Rst CB1 Lockout
Reset Lockout Opto Input to reset CB1 Lockout state
447
Rst CB1 Data
Reset CB1 Maintenance values
448
Block CB1 AR
DDB mapped in PSL from opto or comms input. External signal to force CB1 autoreclose to lockout.
451
Pole Discrep.CB1
Pole discrepancy (from external detector) - input used to force a 2nd single pole trip to move to a 3 pole auto-reclose cycle
452
Loopback Mode
To enable loopback mode via opto input
458
Inhibit WI
Inhibit weak infeed aided scheme logic
459
Test Mode
Commissioning tests - automatically places relay in test mode
460
103 CommandBlock
For IEC-870-5-103 protocol only, used for "Command Blocking" (relay ignores SCADA commands)
461
103 MonitorBlock
For IEC-870-5-103 protocol only, used for "Monitor Blocking" (relay is quiet - issues no messages via SCADA port)
463
Inhibit I>1
Inhibit stage 1 overcurrent protection
464
Inhibit I>2
Inhibit stage 2 overcurrent protection
465
Inhibit I>3
Inhibit stage 3 overcurrent protection
466
Inhibit I>4
Inhibit stage 4 overcurrent protection
467
Inhibit IN>1
Inhibit stage 1 earth fault protection
468
Inhibit IN>2
Inhibit stage 2 earth fault protection
469
Inhibit IN>3
Inhibit stage 3 earth fault protection
470
Inhibit IN>4
Inhibit stage 4 earth fault protection
471
Inhibit V<1
Inhibit stage 1 undervoltage protection
472
Inhibit V<2
Inhibit stage 2 undervoltage protection
473
Inhibit V>1
Inhibit stage 1 overvoltage protection
474
Inhibit V>2
Inhibit stage 2 overvoltage protection
475
Inhibit VN>1
Inhibit stage 2 overvoltage protection
P446SV-TM-EN-1
SIGNAL NAME
DDB_LOGIC_INPUT_TRIP
DDB_LOGIC_INPUT_CLOSE
DDB_LOGIC_INPUT_TRIP_2
DDB_LOGIC_INPUT_CLOSE_2
DDB_RESET_CB_CLOSE_DELAY
DDB_RESET_RELAYS_LEDS
DDB_RESET_THERMAL
DDB_RESET_LOCKOUT
DDB_RESET_ALL_VALUES
DDB_BLOCK_AR
DDB_INP_TR2P
DDB_INTERNAL_LOOPBACK
DDB_INHIBIT_WI
DDB_TEST_MODE
DDB_COMMAND_BLOCKING
DDB_MONITOR_BLOCKING
DDB_INHIBIT_POC1
DDB_INHIBIT_POC2
DDB_INHIBIT_POC3
DDB_INHIBIT_POC4
DDB_INHIBIT_EF1
DDB_INHIBIT_EF2
DDB_INHIBIT_EF3
DDB_INHIBIT_EF4
DDB_INHIBIT_UV1
DDB_INHIBIT_UV2
DDB_INHIBIT_OV1
DDB_INHIBIT_OV2
DDB_INHIBIT_RESOV1
ELEMENT NAME
DESCRIPTION
Appendix B -Settings and Signals