1 PRODUCT DESCRIPTION
Table 1–4: LPS-O DEFAULT OUTPUT CONTACT ASSIGNMENTS
RELAY
DESCRIPTION
T1
TRIP CIRCUIT #1
T2
TRIP CIRCUIT #2
T3
TRIP CIRCUIT #3
T4
TRIP CIRCUIT #4
T5
SPARE
T6
SPARE
A1
MANUAL CLOSE BREAKER 1
A2
MANUAL CLOSE BREAKER 2
A3
BREAKER FAILURE INITIATE #1
A4
BREAKER FAILURE INITIATE #2
A5
RECLOSE INITIATE #1
A6
RECLOSE INITIATE #2
A7
RECLOSE CANCEL
A8
OVERLOAD ALARM
A9
ANY ZONE 1 PHASE DISTANCE FUNCTION
A10
ANY ZONE 2 PHASE DISTANCE FUNCTION
A11
OUT-OF-STEP BLOCKING
A12
OUT-OF-STEP TRIP
KT1
SPARE
KT2
SPARE
KT3
SPARE
KT4
SPARE
C1
NON-CRITICAL ALARM
C2
PT FUSE FAILURE ALARM
In addition to configurable I/O, the LPS-O relay includes the capability for the design of custom logic. This logic
may be used to supplement or to replace the built-in scheme logic. The programmable logic includes the fol-
lowing: up to 40 logic gates (AND, OR, NOT), each with up to 4 inputs; 8 programmable timers, each with a
settable pickup and dropout delay; 8 counters; and 8 latches.
GE Power Management
LPS-O Line Protection System
1.3 CUSTOM PROGRAMMABILITY
MNEMONIC
INDEX
NUMBER
TRIP
33
TRIP
33
TRIP
33
TRIP
33
MNCLS1
58
MNCLS2
59
TRIP
33
TRIP
33
RI
37
RI
37
RC
38
LNOVLD
45
Z1PH
77
Z2PH
78
OSB
120
OST
121
NCALM
52
FF
115

1.3.4 PROGRAMMABLE LOGIC