Chapter 21 - Communications
6.
Move down to the next cell (RP1 Parity). This cell controls the parity format used in the data frames. The
parity can be set to be one of None, Odd or Even. Make sure that the parity format selected on the IED is
the same as that set on the master station.
7.
If the optional fibre optic connectors are fitted, the RP1 PhysicalLink cell is visible. This cell controls the
physical media used for the communication (Copper or Fibre optic).
8.
Move down to the next cell (RP1 Time Sync). This cell affects the time synchronisation request from the
master by the IED. It can be set to enabled or disabled. If enabled it allows the DNP3.0 master to
synchronise the time on the IED.
7.3.9.1
DNP3 CONFIGURATOR
A PC support package for DNP3.0 is available as part of the supplied settings application software (MiCOM S1 Agile)
to allow configuration of the device's DNP3.0 response. The configuration data is uploaded from the device to the
PC in a block of compressed format data and downloaded in a similar manner after modification. The new DNP3.0
configuration takes effect after the download is complete. To restore the default configuration at any time, from
the CONFIGURATION column, select the Restore Defaults cell then select All Settings.
In MiCOM S1 Agile, the DNP3.0 data is shown in three main folders, one folder each for the point configuration,
integer scaling and default variation (data format). The point configuration also includes screens for binary inputs,
binary outputs, counters and analogue input configuration.
If the device supports DNP Over Ethernet, the configuration related settings are done in the folder DNP Over
Ethernet.
7.4

IEC 61850

This section describes how the IEC 61850 standard is applied to General Electric products. It is not a description of
the standard itself. The level at which this section is written assumes that the reader is already familiar with the
IEC 61850 standard.
IEC 61850 is the international standard for Ethernet-based communication in substations. It enables integration of
all protection, control, measurement and monitoring functions within a substation, and additionally provides the
means for interlocking and inter-tripping. It combines the convenience of Ethernet with the security that is so
essential in substations today.
There are two editions of IEC 61850; IEC 61850 edition 1 and IEC 61850 edition 2. The edition which this product
supports depends on your exact model.
560
COMMUNICATIONS
RP1 Parity
None
COMMUNICATIONS
RP1 PhysicalLink
Copper
COMMUNICATIONS
RP1 Time Sync
Enabled