Error Code During Operation; Backup Battery; Mal-Operation During Testing; Failure Of Output Contacts - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

Chapter 25 - Maintenance and Troubleshooting
Test
3.5

ERROR CODE DURING OPERATION

The IED performs continuous self-checking. If the IED detects an error it displays an error message, logs a
maintenance record and after a short delay resets itself. A permanent problem (for example due to a hardware
fault) is usually detected in the power-up sequence. In this case the IED displays an error code and halts. If the
problem was transient, the IED reboots correctly and continues operation. By examining the maintenance record
logged, the nature of the detected fault can be determined.
3.5.1

BACKUP BATTERY

If the IED's self-check detects a failure of the lithium battery, the IED displays an alarm message and logs a
maintenance record but the IED does not reset.
To prevent the IED from issuing an alarm when there is a battery failure, select DATE AND TIME then Battery Alarm
then Disabled. The IED can then be used without a battery and no battery alarm message appears.
3.6

MAL-OPERATION DURING TESTING

3.6.1

FAILURE OF OUTPUT CONTACTS

An apparent failure of the relay output contacts can be caused by the configuration. Perform the following tests to
identify the real cause of the failure. The self-tests verify that the coils of the output relay contacts have been
energized. An error is displayed if there is a fault in the output relay board.
Test
1
Is the Out of Service LED ON?
Examine the Contact status in the Commissioning
2
section of the menu.
Examine the fault record or use the test port to check the
3
protection element is operating correctly.
Using the Commissioning or Test mode function, apply a
test pattern to the relevant relay output contacts.
4
Consult the correct external connection diagram and use
a continuity tester at the rear of the relay to check the
relay output contacts operate.
3.6.2

FAILURE OF OPTO-INPUTS

The opto-isolated inputs are mapped onto the IED's internal DDB signals using the programmable scheme logic. If
an input is not recognised by the scheme logic, use the Opto I/P Status cell in the COMMISSION TESTS column to
check whether the problem is in the opto-input itself, or the mapping of its signal to the scheme logic functions.
If the device does not correctly read the opto-input state, test the applied signal. Verify the connections to the
opto-input using the wiring diagram and the nominal voltage settings in the OPTO CONFIG column. To do this:
1.
Select the nominal voltage for all opto-inputs by selecting one of the five standard ratings in the Global
Nominal V cell.
2.
Select Custom to set each opto-input individually to a nominal voltage.
3.
Using a voltmeter, check that the voltage on its input terminals is greater than the minimum pick-up level
(See the Technical Specifications chapter for opto pick-up levels).
676
Check
Check
The VT type field in the model number is incorrect (no VTs
8
fitted)
If this LED is ON, the relay may be in test mode or the protection has
been disabled due to a hardware verify error.
If the relevant bits of the contact status are operated, go to test 4; if not,
go to test 3.
If the protection element does not operate, check the test is correctly
applied.
If the protection element operates, check the programmable logic to
make sure the protection element is correctly mapped to the contacts.
If the output relay operates, the problem must be in the external wiring
to the relay. If the output relay does not operate the output relay
contacts may have failed (the self-tests verify that the relay coil is being
energized). Ensure the closed resistance is not too high for the continuity
tester to detect.
Action
Action
P446SV-TM-EN-1