GE MiCOM P40 Technical Manual page 793

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
MENU TEXT
commands will be ignored (i.e. CB Trip/Close, change setting group etc.). When in this mode the relay returns a "negative acknowledgement
of command" message to the master station.
RP1 Card Status
Displays the status of the card in RP1
RP1 Port Config
Courier versions only. This cell defines whether an electrical KBus or EIA(RS)485 is being used for communication between the master station
and relay.
RP1 Comms Mode
Courier versions only. The choice is either IEC 60870 FT1.2 for normal operation with 11-bit modems, or 10-bit no parity.
RP1 Baud Rate
Courier versions only. This cell controls the communication speed between relay and master station. It is important that both relay and
master station are set at the same speed setting.
Meas Scaling
DNP 3.0 versions only. Setting to report analogue values in terms of primary, secondary or normalized (with respect to the CT/VT ratio
setting) values.
Message Gap (ms)
DNP 3.0 versions only. This setting allows the master station to have an interframe gap.
DNP Need Time
DNP 3.0 versions only. The duration of time waited before requesting another time sync from the master.
DNP App Fragment
DNP 3.0 versions only. The maximum message length (application fragment size) transmitted by the relay.
DNP App Timeout
DNP 3.0 versions only. Duration of time waited, after sending a message fragment and awaiting a confirmation from the master.
DNP SBO Timeout
DNP 3.0 versions only. Duration of time waited, after receiving a select command and awaiting an operate confirmation from the master.
DNP Link Timeout
DNP 3.0 versions only. Duration of time that the relay will wait for a Data Link Confirm from the master. A value of 0 means data link support
disabled and 1 to 120 seconds is the timeout setting.
Class 0 Poll
Used for DNP3 serial only.
When set the cell to "Running Counters", the IED will only report the static counters (object 20) in class 0 responses. Otherwise if set to
"Frozen Counters", the IED will only report the frozen counters (object 21) in class 0 responses.
NIC Protocol
IEC61850 versions only. Indicates that IEC 61850 will be used on the rear Ethernet port.
NIC Mac Address
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
0E
0B
0E
0C
K Bus
0E
0D
IEC60870 FT1.2
0E
0E
19200 bits/s
0E
0F
Normalised
0E
10
0
0E
11
10
0E
12
2048
0E
13
2
0E
14
10
0E
15
0
0E
16
Running Counters
0E
1F
IEC61850
0E
22
DESCRIPTION
K Bus OK
EIA485 OK
Fibre Optic OK
[Indexed String]
K Bus
EIA485 (RS485)
[Indexed String]
IEC60870 FT1.2 Frame
10-bit no parity
[Indexed String]
9600 bits/s
19200 bits/s
38400 bits/s
[Indexed String]
Normalised
Primary
Secondary
[Indexed String]
Message Gap (ms)
[Courier Number (time-milliseconds)]
From 1 to 30 in steps of 1
[Courier Number (time-minutes)]
From 100 to 2048 in steps of 1
[Unsigned Integer (32 bits)]
From 1 to 120 in steps of 1
[Courier Number (time-seconds)]
From 1 to 10 in steps of 1
[Courier Number (time-seconds)]
From 0 to 120 in steps of 1
[Courier Number (time-seconds)]
0 or 1
[Indexed String]
UCA 2.0
UCA 2.0 GOOSE
IEC61850
DNP3.0
[Indexed String]
NIC Mac Address
[ASCII Text (17 Chars)]
Appendix B -Settings and Signals
AVAILABLE OPTIONS
B47

Advertisement

Table of Contents
loading