Overfrequency Protection Logic; Application Notes; Figure 223: Overfrequency Logic (Single Stage) - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

Chapter 15 - Frequency Protection Functions
2.2.2

OVERFREQUENCY PROTECTION LOGIC

Averaging
Freq
Freq
F>1 Setting
F>1 Setting
F>1 Status
F>1 Status
Enabled
Enabled
All Poles Dead
All Poles Dead
Freq Not Found
Freq Not Found
F>1 Timer Block
F>1 Timer Block

Figure 223: Overfrequency logic (single stage)

If the frequency is above the setting and not blocked, the DT timer is started and after this has timed out, the trip is
produced. If the frequency cannot be determined, the function is blocked.
2.2.3

APPLICATION NOTES

2.2.3.1
SETTING GUIDELINES
Following changes on the network caused by faults or other operational requirements, it is possible that various
subsystems will be formed within the power network. It is likely that these subsystems will suffer from a
generation/load imbalance. The "islands" where generation exceeds the existing load will be subject to
overfrequency conditions. Severe over frequency conditions may be unacceptable to many industrial loads, since
running speeds of motors will be affected. The overfrequency element can be suitably set to sense this
contingency.