GE MiCOM P40 Technical Manual page 908

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

Appendix B -Settings and Signals
ORDINAL
Front panel miniature battery failure - either battery removed from slot, or low voltage
353
Field Volts Fail
48V field voltage failure
354
Rear Comm 2 Fail
Comm2 hardware failure - second rear communications board
355
GOOSE IED Absent
The IED is not subscribed to a publishing IED in the current scheme
356
NIC Not Fitted
Ethernet board not fitted
357
NIC No Response
Ethernet board not responding
358
NIC Fatal Error
Ethernet board unrecoverable error
359
NIC Soft. Reload
Ethernet problem
360
Bad TCP/IP Cfg.
Ethernet problem
361
Bad OSI Config.
Ethernet problem
362
NIC Link Fail
Ethernet link lost
363
NIC SW Mis-Match
Ethernet board software not compatible with main CPU
364
IP Addr Conflict
The IP address of the IED is already used by another IED
365
IM Loopback
EIA(RS)232 InterMiCOM indication that Loopback testing is in progress
366
IM Message Fail
EIA(RS)232 InterMiCOM Message Failure alarm. Setting that is used to alarm for poor channel quality. If during the fixed 1.6 s rolling
window the ratio of invalid messages to the total number of messages that should be received (based upon the 'Baud Rate' setting)
exceeds the above threshold, a 'Message Fail' alarm will be issued
367
IM Data CD Fail
EIA(RS)232 InterMiCOM Data Channel Detect Fail i.e. modem failure
368
IM Channel Fail
EIA(RS)232 InterMiCOM Channel Failure alarm. No messages were received during the alarm time setting
369
Backup Setting
This is an alarm that is ON if any setting fail during the setting changing process. If this happens, the relay will use the last known
good setting
370
Reserved
Platform Alarm 19
371
Reserved
Platform Alarm 20
372
SNTP Failure
SNTP synchronisation fail alarm
373
NIC MemAllocFail
MMS library memory allocation failure
374
PTP Failure
IEEE 1588 PTP time synchronisation failure alarm
375
Reserved
Platform Alarm 24
376
Reserved
Platform Alarm 25
377
BBRAM Failure
BBRAM Verify Fail
378
Reserved
Platform Alarm 27
379
Reserved
Platform Alarm 28
B162
SIGNAL NAME
DDB_FIELD_VOLTS_FAIL
DDB_REAR_COMMS_FAIL
DDB_GOOSE_MISSING_IED
DDB_ECARD_NOT_FITTED
DDB_NIC_NOT_RESPONDING
DDB_NIC_FATAL_ERROR
DDB_NIC_SOFTWARE_RELOAD
DDB_INVALID_NIC_TCPIP_CONFIG
DDB_INVALID_NIC_OSI_CONFIG
DDB_NIC_LINK_FAIL
DDB_SW_MISMATCH_ALARM
DDB_NIC_IP_ADDRESS_CONFLICT
DDB_INTERMICOM_LOOPBACK
DDB_INTERMICOM_MESSAGE
DDB_INTERMICOM_DCD
DDB_INTERMICOM_CHANNEL
DDB_BACKUP_DATA_IN_USE
DDB_PLATFORM_ALARM_19
DDB_PLATFORM_ALARM_20
DDB_SNTP_FAIL_ALARM
DDB_NIC_MEM_ALLOC_FAIL_ALARM
DDB_PTP_FAIL_ALARM
DDB_PLATFORM_ALARM_24
DDB_PLATFORM_ALARM_25
DDB_BBRAM_VERIFY_FAIL
DDB_PLATFORM_ALARM_27
DDB_PLATFORM_ALARM_28
ELEMENT NAME
DESCRIPTION
P446SV
P446SV-TM-EN-1