GE MiCOM P40 Technical Manual page 927

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
ORDINAL
995
Vsc2 Select 1x
Switch Vsc2 input signal 1 among three designated Logical Node on Ethernet for IEC 61850-9-2LE.
996
DEF Forward
DEF forward (directional earth fault aided scheme detector)
997
DEF Reverse
DEF reverse (directional earth fault aided scheme detector)
998
Delta Dir FWD AN
Delta directional scheme forward AN detection
999
Delta Dir FWD BN
Delta directional scheme forward BN detection
1000
Delta Dir FWD CN
Delta directional scheme forward CN detection
1001
Delta Dir FWD AB
Delta directional scheme forward AB detection
1002
Delta Dir FWD BC
Delta directional scheme forward BC detection
1003
Delta Dir FWD CA
Delta directional scheme forward CA detection
1004
Delta Dir Rev AN
Delta directional scheme reverse AN detection
1005
Delta Dir Rev BN
Delta directional scheme reverse BN detection
1006
Delta Dir Rev CN
Delta directional scheme reverse CN detection
1007
Delta Dir Rev AB
Delta directional scheme reverse AB detection
1008
Delta Dir Rev BC
Delta directional scheme reverse BC detection
1009
Delta Dir Rev CA
Delta directional scheme reverse CA detection
1010
Phase Select A
Phase selector - phase A pickup
1011
Phase Select B
Phase selector - phase B pickup
1012
Phase Select C
Phase selector - phase C pickup
1013
Phase Select N
Phase selector - neutral indication
1014
P Swing Detector
Power swing detected
1015
PSB Fault
Power swing block fault
1016
Ih(2) Loc Blk A
2nd harmonic current ratio exceeds threshold on phase A (may be used to block any instantaneous distance elements that reach
through the reactance of a power transformer)
1017
Ih(2) Loc Blk B
2nd harmonic current ratio exceeds threshold on phase B (may be used to block any instantaneous distance elements that reach
through the reactance of a power transformer)
1018
Ih(2) Loc Blk C
2nd harmonic current ratio exceeds threshold on phase C (may be used to block any instantaneous distance elements that reach
through the reactance of a power transformer)
1019
Ih(2) Loc Blk N
2nd harmonic current ratio exceeds threshold on neutral current measurement (may be used to block any instantaneous distance
elements that reach through the reactance of a power transformer)
1024
LED 1
Programmable LED 1
1025
LED 2
Programmable LED 2
P446SV-TM-EN-1
SIGNAL NAME
DDB_9_2_VSC2_SELECT_1X
DDB_DEF_FWD
DDB_DEF_REV
DDB_DELTA_DIR_FWD_AN
DDB_DELTA_DIR_FWD_BN
DDB_DELTA_DIR_FWD_CN
DDB_DELTA_DIR_FWD_AB
DDB_DELTA_DIR_FWD_BC
DDB_DELTA_DIR_FWD_CA
DDB_DELTA_DIR_REV_AN
DDB_DELTA_DIR_REV_BN
DDB_DELTA_DIR_REV_CN
DDB_DELTA_DIR_REV_AB
DDB_DELTA_DIR_REV_BC
DDB_DELTA_DIR_REV_CA
DDB_PHS_SEL_A
DDB_PHS_SEL_B
DDB_PHS_SEL_C
DDB_PHS_SEL_N
DDB_PSB_DETECTED
DDB_PSB_FAULT
DDB_HARMONIC_2_A
DDB_HARMONIC_2_B
DDB_HARMONIC_2_C
DDB_HARMONIC_2_N
DDB_OUTPUT_LED_1
DDB_OUTPUT_LED_2
ELEMENT NAME
DESCRIPTION
Appendix B -Settings and Signals
B181