Appendix B -Settings and Signals
MENU TEXT
Reset All Values
CB CONTROL
This column controls the circuit Breaker Control configuration
CB Control by
Selects the type of circuit breaker control to be used
Close Pulse Time
Set period during which the CB should close when a CB close command is issued.
Trip Pulse Time
Set period during which the CB should trip when a CB trip command is issued.
Man Close Delay
Set delay after operator controlled CB close sequence is initiated, before a CB close output can be issued. (Allows operator to retire to a place
of safety before the CB close command is issued).
CB Healthy Time
Maximum waiting time for input DDB: CB1 Healthy (= gas pressure OK, spring charged etc) to enable CB1 Close by manual control. Same
setting applies to DDB: CB2 Healthy to enable CB2 Close by manual control. If set time runs out with input DDB: CBx Healthy low (= 0), alarm
Control CBx Unhealthy is set and CB close sequence is cancelled.
Check Sync Time
Maximum waiting time for input signal CB1MSCOK from system check logic, to enable CB1 Close by manual control. Same setting applies to
input signal CB2MSCOK to enable CB2 Close by manual control. If set time runs out with input signal CBxMSCOK low (= 0), alarm Control CBx
NoChSync is set and CB close sequence is cancelled.
CB mon LO reset
Command to reset the CB monitoring Lockout Alarm
Rst CB mon LO by
Setting that determines if a lockout condition caused by CB monitoring conditions will be reset by a manual circuit breaker close command
or via the user interface.
CB mon LO RstDly
If Rst CB mon LO by is set to CB close then CB mon LO RstDly timer allows reset of CB lockout state after set time delay
Autoreclose Mode
Command to changes state of Auto-Reclose
AR Status
Auto Reclose - Inservice / Out of service
CB Status Input
B20
COL
ROW
DEFAULT SETTING
07
00
07
01
Disabled
07
02
0.5
07
03
0.5
07
05
10
07
06
5
07
07
5
07
08
No
07
09
CB Close
07
0A
5
07
0B
No Operation
07
0E
07
11
52B 1 pole
DESCRIPTION
Disabled
Local
Remote
Local+Remote
Opto
Opto+local
Opto+Remote
Opto+Rem+local
[Indexed String]
From 0.1 to 10 in steps of 0.01
[Courier Number (time-seconds)]
From 0.1 to 5 in steps of 0.01
[Courier Number (time-seconds)]
From 0.01 to 600 in steps of 0.01
[Courier Number (time-seconds)]
From 0.01 to 9999 in steps of 0.01
[Courier Number (time-seconds)]
From 0.01 to 9999 in steps of 0.01
[Courier Number (time-seconds)]
No
Yes
[Indexed String]
User Interface
CB Close
[Indexed String]
From 0.1 to 600 in steps of 0.01
[Courier Number (time-seconds)]
No Operation
In Service
Out of Service
[Indexed String]
Out of Service
In Service
[Indexed String]
None
52A 3 pole
52B 3 pole
52A & 52B 3 pole
52A 1 pole
52B 1 pole
52A & 52B 1 pole
AVAILABLE OPTIONS
P446SV-TM-EN-1
P446SV