Accessing setpoints via the front panel
Logic inputs
Logic inputs are connected as indicated below. Ensure correct polarity and do not connect
any logic input circuits to ground or else relay hardware may be damaged. External
contacts can be connected to the relay's fourteen (14) logic inputs. As shown, these
contacts can be either dry or wet. It is also possible to use a combination of both contact
types.
Dry Contact Connection
750/760 RELAY
+32 V DC
Logic Input 1
32 V DC
DC Negative
Analog inputs and outputs
Analog Inputs and Outputs are connected as indicated in the Typical Wiring Diagram. Also
refer to the figure below. Note that the shield of the cable shall be grounded at one point
only, usually at the PLC/computer end only.
ACCESSING SETPOINTS VIA THE FRONT PANEL
Refer to Chapter 1 750/760 instruction manual for details on changing setpoints. To have
access to the relay setpoints, you must install a hardware jumper across terminals C10 and
C11 at the back of the relay case. Attempts to enter a new setpoint without this electrical
connection will result in an error message. Additional information is provided in the same
section regarding passcodes and accessing information via the serial ports of the relay.