5.7.1

RESET CB LOCKOUT LOGIC DIAGRAM

Res LO by CB IS
Enabled
CB1CRLo
Res LO by UI
Enabled
Reset CB1 LO
Yes
Res LO by NoAR
Enabled
ARDisabled
Num CBs
CB2 Only
Res LO by ExtDDB
Enabled
Rst CB1 Lockout
Res LO by TDelay
Enabled
LO Reset Time
CB1 AR Lockout
Res LO by CB IS
Enabled
CB2CRLo
Res LO by UI
Enabled
Reset CB2 LO
Yes
Res LO by NoAR
Enabled
ARDisabled
Num CBs
CB2 Only
Res LO by ExtDDB
Enabled
Rst CB2 Lockout
Res LO by TDelay
Enabled
LO Reset Time
CB2 AR Lockout
Figure 233: Reset Circuit Breaker Lockout Logic Diagram (Modules 57 & 58)
5.8

APPLICATION NOTES

5.8.1

SETTING THE THRESHOLDS FOR THE TOTAL BROKEN CURRENT

Where power lines use oil circuit breakers (OCBs), changing of the oil accounts for a significant proportion of the
switchgear maintenance costs. Often, oil changes are performed after a fixed number of CB fault operations.
However, this may result in premature maintenance where fault currents tend to be low, because oil degradation
may be slower than would normally be expected. The Total Current Accumulator (I^ counter) cumulatively stores
the total value of the current broken by the circuit breaker providing a more accurate assessment of the circuit
breaker condition.