Circuit Breaker In Service Logic Diagram; Autoreclose Enable Logic; Autoreclose Enable Logic Diagram; Autoreclose Leader/Follower - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

Chapter 11 - Autoreclose
5.3.1

CIRCUIT BREAKER IN SERVICE LOGIC DIAGRAM

CB1 AR Lockout
Num CBs
CB1 Only
Both CB 1&CB2
CB1 Closed 3 ph
CB1 ARIP
CB2 AR Lockout
Num CBs
CB2 Only
Both CB 1&CB2
CB2 Closed 3 ph
CB2 ARIP
V03303

Figure 151: CB In Service logic diagram (Module 4)

5.4

AUTORECLOSE ENABLE LOGIC

The Autoreclose function must be enabled in the CONFIGURATION column before it can be brought into service. It
can be brought into service by:
using an opto-input mapped to the AR Enable DDB signal
pulsing the DDB signal AR On Pulse (use AR Off Pulse to bring it out of service)
programming a function key on the HMI.
if applicable, using IEC 60870-5-103 communications
Further validation signals are also required to switch on Autoreclose. These are the DDB signals AR Enable CB1
and AR Enable CB2. Once Autoreclose is in service, the AR In Service DDB signal is asserted and the AR Status cell
in the CB CONTROL column is set accordingly.
5.4.1

AUTORECLOSE ENABLE LOGIC DIAGRAM

Auto-Reclose
Enable
HMI Comand
IEC 60870 Comand
AR On Pulse
AR OFF Pulse
AR Enable
*
AR Enable CB1
AR Enable CB2
*
V03301

Figure 152: Autoreclose Enable logic diagram (Module 5)

5.5

AUTORECLOSE LEADER/FOLLOWER

You can select either CB1 or CB2 to be the leader, with CB2 or CB1 as the follower respectively.
292
CBIST
&
1
CBIST
&
Logic 1
CBIST
&
1
CBIST
&
Logic 1
Autoreclose
Status
1
Default = ON
1382
1383
1384
1609
1
1605
0
CBISMT
&
1
0
CBISMT
&
1
&
*Defaults to High if not mapped in PSL
CB1 CRLO
S
Q
CB1 In Service
R
CB2 CRLO
S
Q
CB2 In Service
R
AR DISABLED
1385
AR In Service
P446SV-TM-EN-1