Chapter 11 - Autoreclose
Signal Name
FollSPAROK
AR Modes Enable (9)
InitAR
AR Initiation (11)
Invalid_AR_Mode
AR Modes Enable (9)
LastShot
Sequence Counter (18)
OKTimeSP
1-phase AR Dead Time (24) Dead Time Start Enable (22)
Leader/Follower CB
PrefLCB1
Selection (6)
Leader/Follower CB
PrefLCB2
Selection (6)
ProtARBlock
AR Initiation (11)
ProtRe_Op
Evolving Fault (20)
ResCB1ARSucc
Successful AR Signals (36)
ResCB1Lo
Reset CB Lockout (57)
ResCB2ARSucc
ResCB2Lo
ResetL-F
Evolving Fault (20)
ResPRMem
CB1-pole / 3-pole trip (13)
SCIncrement
Sequence Counter (18)
SCCountoveqShots
Leader/Follower
SetLCB1
Logic 1 & 2 (7)
Leader/Follower
SetLCB2
Logic 1 & 2 (7)
Prepare Reclaim Initiation
SetCB13PCl
(34)
Prepare Reclaim Initiation
SetCB1SPCl
(34)
SetCB23PCl
SetCB2SPCl
SPDTComp
CB1-pole / 3-pole trip (13),
TAR2/3Ph
CB2 1-pole / 3-pole trip (14)
276
Source
Leader/Follower (7)
AR Initiation (11)
CB1-pole / 3-pole trip (13)
CB2 1-pole / 3-pole trip (14)
CB1 AR In Progress (16)
CB2 AR In Progress (17)
Autoreclose Lockout (55)
Evolving Fault (20)
Autoreclose Lockout (55)
Leader/Follower (7)
Leader/Follower (7)
Autoreclose Lockout (55)
Autoreclose Lockout (55)
Sequence Counter (18)
1-phase AR Cycle Selection (19)
Evolving Fault (20)
Successful AR Signals (36)
AR Reset Successful (37)
Autoreclose Lockout (55)
Leader/Follower (7)
1-phase AR Cycle Selection (19)
CB2 1-pole / 3-pole trip (14)
Fault Memory (15)
Leader/Follower (7)
Leader/Follower (7)
Reclaim Time (35)
Successful AR Signals (36)
Reclaim Time (35)
Successful AR Signals (36)
Reclaim Time (35)
Reclaim Time (35)
CB Trip Time Monitor (53)
Destination
The follower circuit breaker is Ok for single-
phase Autoreclose
Internally derived signal to initiate
Autoreclose (external triggers not included)
An invalid state is being indicated by the
logic that uses opto-inputs to determine
the Autoreclose mode.
Idicates tha the Autoreclose sequence has
reached the last shot
The dead time for single pole Autoreclose is
OK
CB1 is the preferred leader
CB2 is the preferred leader
Signal to block Autoreclose for selected
host protection elements
Signal to indicate that further protection
operation has occurred during Autoreclose
Reset the indication of successful
Autoreclose for CB1
Reset the indication of lockout for CB1
Reset the indication of successful
Autoreclose for CB2
Reset the indication of lockout for CB2
Used to reset the allocation of leader/
follower functionality
Reset the signal that indicates the faulted
phases that initiated the Autoreclose
Increment the sequence counter
Sequence counter has exceeded setting
CB1 has been selected as leader
CB2 has been selected as leader
Three-phase close command to CB1
Single-phase close command to CB1
Three-phase close command to CB2
Single-phase close command to CB2
Single-phase dead time complete
A 2-phase or 3-phase trip has initiated
Autoreclose for CB1 (as leader)
P446SV
Description
P446SV-TM-EN-1