P446SV
MENU TEXT
Setting of ZP residual compensation angle.
kZmP Mut. Comp.
Setting of ZP mutual compensation magnitude.
kZmP Mut. Angle
Setting of ZP mutual compensation angle.
RP Gnd Resistive
Setting for ZP ground resistive reach.
ZP Sensit Ignd>P
Zone P current sensitivity.
Z4 Gnd. Reach
Setting for Z4 reach. This is a common setting for Z4 time delayed and Z4 high speed elements used in blocking schemes and for current
reversal guard.
Z4 Gnd. Angle
Setting of line angle (positive sequence) for zone 4.
Z4 Dynamic Tilt
Setting that enables or disables Z4 top reactance line dynamic tilting. If set enabled, the top line angle will be automatically shifted by the
angle difference between the fault current and negative sequence current, starting from the 'Z4 Tilt top line' angle setting – see the next cell.
The Z4, as over-reaching zone, is allowed only to tilt up. If Dynamic tilting is disabled, the top line will be shifted by the 'Z4 Tilt top line' setting
(Predetermined tilting by fixed angle).
This setting is visible only when ground characteristic is set to 'Quad'.
Z4 Tilt Top Line
Setting of the Z4 tilt angle. Minus angle tilts the reactance line downwards This setting is visible only when the above setting is visible.
kZN4 Res. Comp.
Setting of Z4 residual compensation magnitude.
kZN4 Res. Angle
Setting of Z4 residual compensation angle.
kZm4 Mut. Comp.
Setting of Z4 mutual compensation magnitude.
kZm4 Mut. Angle
Setting of Z4 mutual compensation angle.
R4 Gnd Resistive
Setting for Z4 ground resistive reach.
Z4 Sensit Ignd>4
Zone 4 current sensitivity.
GROUP 1: SCHEME
LOGIC
This column contains settings for Distance Scheme Logic
Zone1 Tripping
Setting to select for which types of fault Zone 1 elements will be applied.
tZ1 Ph. Delay
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
32
87
1
32
88
0
32
89
20
32
8B
0.05
32
90
15
32
91
70
32
93
Enabled
32
94
-3
32
95
1
32
96
0
32
97
1
32
98
0
32
99
15
32
9B
0.05
34
00
34
08
Phase And Ground
34
09
0
DESCRIPTION
[Courier Number (angle)]
From 0 to 10 in steps of 0.01
[Courier Number]
From -180 to 90 in steps of 0.1
[Courier Number (angle)]
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
From 0.05*I1 to 2*I1 in steps of 0.005*I1
[Courier Number (current)]
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
From 20 to 90 in steps of 1
[Courier Number (angle)]
Disabled
Enabled
[Indexed String]
From -30 to 30 in steps of 1
[Courier Number (angle)]
From 0 to 10 in steps of 0.01
[Courier Number]
From -180 to 90 in steps of 0.1
[Courier Number (angle)]
From 0 to 10 in steps of 0.01
[Courier Number]
From -180 to 90 in steps of 0.1
[Courier Number (angle)]
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
From 0.05*I1 to 2*I1 in steps of 0.005*I1
[Courier Number (current)]
Disabled
Phase only
Ground only
Phase And Ground
[Indexed String]
From 0 to 10 in steps of 0.01
Appendix B -Settings and Signals
AVAILABLE OPTIONS
B103