P446SV
7

INPUT / OUTPUT CONNECTIONS

7.1

ISOLATED DIGITAL INPUTS

Compliance
Rated nominal voltage
Operating range
Withstand
Recognition time with half-cycle ac
immunity filter removed
Recognition time with filter on
7.1.1

NOMINAL PICKUP AND RESET THRESHOLDS

Nominal battery
voltage
24/27 V
Logic 0 < 16.2V, Logic 1 > 19.2V
30/34
Logic 0 < 20.4V, Logic 1 > 24V
48/54
Logic 0 < 32.4V, Logic 1 > 38.4V
110/125
Logic 0 < 75V, Logic 1 > 88V
220/250
Logic 0 < 150V, Logic 1 > 176V
Note:
Filter is required to make the opto-inputs immune to induced AC voltages.
In addition to the above thresholds, some models of this product provide the following threshold levels for FSK
applications:
For 220/250 voltage inputs: Logic 0 < 145V, Logic 1 > 165V
7.2

STANDARD OUTPUT CONTACTS

Compliance
Use
Rated voltage
Maximum continuous current
Short duration withstand carry
Make and break, dc resistive
Make and break, dc inductive
Make and break, ac resistive
Make and break, ac inductive
Make and carry, dc resistive
Make, carry and break, dc resistive
P446SV-TM-EN-1
Opto-isolated digital inputs (opto-inputs)
ESI 48-4
24 to 250 V dc
19 to 265 V dc
300 V dc
< 2 ms
< 12 ms
Logic levels: 60-80% DO/PU
In accordance with IEC 60255-1:2009
General purpose relay outputs for signalling, tripping and alarming
300 V
10 A
30 A for 3 s
250 A for 30 ms
50 W
62.5 W (L/R = 50 ms)
2500 VA resistive (cos phi = unity)
2500 VA inductive (cos phi = 0.7)
30 A for 3 s, 10000 operations (subject to the above limits)
4 A for 1.5 s, 10000 operations (subject to the above limits)
Chapter 26 - Technical Specifications
Logic Levels: 50-70% DO/PU
Logic 0 <12V, Logic 1 > 16.8V
Logic 0 < 15V, Logic 1 > 21V
Logic 0 < 24V, Logic 1 > 33.6V
Logic 0 < 55.V, Logic 1 > 77V
Logic 0 < 110V, Logic 1 > 154V
699