Figure 282: Data model layers in IEC 61850
The levels of this hierarchy can be described as follows:
Data Frame format
Layer
Physical Device
Logical Device
Wrapper/Logical Node Instance
Data Object
Data Attribute
7.4.4

IEC 61850 IN MICOM IEDS

IEC 61850 is implemented by use of a separate Ethernet card. This Ethernet card manages the majority of the
IEC 61850 implementation and data transfer to avoid any impact on the performance of the protection functions.
To communicate with an IEC 61850 IED on Ethernet, it is necessary only to know its IP address. This can then be
configured into either:
An IEC 61850 client (or master), for example a bay computer (MiCOM C264)
An HMI
An MMS browser, with which the full data model can be retrieved from the IED, without any prior knowledge
of the IED
562
stVal
q
Pos
LN1: XCBR
Logical Device : IEDs 1 to n
Physical Device (network address)
Identifies the actual IED within a system. Typically the device's name or IP address can be used (for
example Feeder_1 or 10.0.0.2.
Identifies groups of related Logical Nodes within the Physical Device. For the MiCOM IEDs, 5 Logical
Devices exist: Control, Measurements, Protection, Records, System.
Identifies the major functional areas within the IEC 61850 data model. Either 3 or 6 characters are
used as a prefix to define the functional group (wrapper) while the actual functionality is identified by
a 4 character Logical Node name suffixed by an instance number.
For example, XCBR1 (circuit breaker), MMXU1 (measurements), FrqPTOF2 (overfrequency protection,
stage 2).
This next layer is used to identify the type of data you will be presented with. For example, Pos
(position) of Logical Node type XCBR.
This is the actual data (measurement value, status, description, etc.). For example, stVal (status value)
indicating actual position of circuit breaker for Data Object type Pos of Logical Node type XCBR.
Data Attributes
t
PhA
Data Objects
Logical Nodes : 1 to n
LN2: MMXU
Description
PhB
PhC
A
P446SV