Reset Cb Lockout Logic Diagram; Pole Discrepancy; Figure 186: Reset Circuit Breaker Lockout Logic Diagram (Modules 57 & 58) - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
5.20.1

RESET CB LOCKOUT LOGIC DIAGRAM

Res LO by CB IS
Enabled
CB1CRLo
Res LO by UI
Enabled
Reset CB1 LO
Yes
Res LO by NoAR
Enabled
ARDisabled
Num CBs
CB2 Only
Res LO by ExtDDB
Enabled
Rst CB1 Lockout
Res LO by TDelay
Enabled
LO Reset Time
CB1 AR Lockout
Res LO by CB IS
Enabled
CB2CRLo
Res LO by UI
Enabled
Reset CB2 LO
Yes
Res LO by NoAR
Enabled
ARDisabled
Num CBs
CB2 Only
Res LO by ExtDDB
Enabled
Rst CB2 Lockout
Res LO by TDelay
Enabled
LO Reset Time
CB2 AR Lockout
Figure 186: Reset Circuit Breaker Lockout Logic Diagram (Modules 57 & 58)
5.21

POLE DISCREPANCY

In a three-pole CB, certain combinations of poles open and closed are indicative of a problem. The Pole
Discrepancy Logic combines an indication of a Pole Discrepancy condition from the CB Monitoring logic with
signals from the internal Autoreclose logic to produce a combined Pole Discrepancy indication for the CB.
P446SV-TM-EN-1
&
&
&
1
&
446
&
t
306
0
&
&
&
1
&
1422
&
t
328
0
1
1
Chapter 11 - Autoreclose
ResCB1Lo
ResCB2Lo
V03383
329