GE MiCOM P40 Technical Manual page 841

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
MENU TEXT
the value as long as 'Simple' mode setting remains active.
Advanced setting mode:
'Advanced' setting mode allows individual distance ohmic reaches and residual compensation factors to be entered for each zone. When
'Advanced' mode is selected, all 'percentage' settings that are associated to 'Simple' setting mode in the column GROUP x DISTANCE SETUP
will be hidden and the Distance zone settings need to be entered for each zone in the 'GROUP x DIST. ELEMENTS' column.
PHASE DISTANCE
Phase Chars.
Setting to disable (turn off) phase distance protection or to set Mho or Quad operating characteristic: ANSI 21P.
The chosen setting is applicable to all phase distance zones.
Quad Resistance
Setting to define the mode of resistive reach coverage. If 'Common' mode is selected, all phase distance zones will have the equal resistive
coverage. If 'Proportional' mode is selected, the zones will have resistive coverage according to the % reach set for the zone, multiplied by
the 'Fault Resistance' RPH setting.
This setting is visible only when 'Simple' setting mode and quad characteristic are set.
Fault Resistance
Setting used to specify the fault arc resistance that can be detected for faults between phases. The set value determines the right hand side
of the quadrilaterals.
This setting is visible only when 'Simple' setting mode and quad characteristic are set.
Zone 1 Ph Status
To enable (activate) or disable (turn off) or enable (only in the case that differential protection communication channel is lost) Z1 for phase
faults.
This setting is invisible if 'Phase Char.' is disabled.
Zone 1 Ph Reach
Setting entry as percentage of the line impedance that sets Zone 1 reach in ohms.
Zone 2 Ph Status
To enable (activate) or disable (turn off) or enable (only in the case that differential protection communication channel is lost) Z2 for phase
faults.
This setting is invisible if 'Phase Char.' is disabled.
Zone 2 Ph Reach
Setting entry as percentage of the line impedance that sets Zone 2 reach in ohms.
Zone 3 Ph Status
To enable (activate) or disable (turn off) or enable (only in the case that differential protection communication channel is lost) Z3 for phase
faults.
This setting is invisible if 'Phase Char.' is disabled.
Zone 3 Ph Reach
Setting entry as percentage of the line impedance that sets Zone 3 forward reach in ohms.
Zone 3 Ph Offset
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
31
10
31
11
Mho
31
12
Proportional
31
13
10
31
20
Enabled
31
21
80
31
30
Enabled
31
31
150
31
40
Enabled
31
41
250
31
42
Enabled
DESCRIPTION
Disabled
Mho
Quadrilateral
Disabled
Mho
[Indexed String]
Common
Proportional
[Indexed String]
From 0.1*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
Disabled
Enabled
Enabled Ch Fail
[Indexed String]
From 10 to 1000 in steps of 1
[Courier Number (percentage)]
Disabled
Enabled
Enabled Ch Fail
[Indexed String]
From 10 to 1000 in steps of 1
[Courier Number (percentage)]
Disabled
Enabled
Enabled Ch Fail
[Indexed String]
From 10 to 1000 in steps of 1
[Courier Number (percentage)]
Disabled
Enabled
[Indexed String]
Appendix B -Settings and Signals