3.1

MHO CHARACTERISTICS

There are different types of Mho characteristic, but two specific ones are well suited to introducing the defining
principles. These are the directional Self-polarized Mho and the Offset Mho. Both types are used for both phase
faults and earth faults.
In practice, self-polarized Mhos are rarely used since voltage collapses for close-up faults render self-polarization
unreliable. Rather, memory-polarization components and/or cross-polarization components are usually used to
provide a polarizing reference. Directional Self-Polarized Mhos, however, are simpler to understand and are used
by way of introduction.
3.1.1

DIRECTIONAL MHO CHARACTERISTIC FOR PHASE FAULTS

The following diagram illustrates how the Directional Self-Polarized Mho characteristic for phase Distance
protection is created.
V02710

Figure 34: Directional mho element construction

The two signals provided to the comparator are:
S
= V
1
S
= V - I.Z
2
Operation occurs when the angle between the signals is greater than 90°
3.1.2

OFFSET MHO CHARACTERISTIC FOR PHASE FAULTS

The following diagram illustrates how the Offset Mho characteristic for phase Distance protection is created:
P446SV-TM-EN-1
I 
Z
V
Chapter 7 - Distance Protection
V
I
Z
90°
I
111