P446SV
MENU TEXT
ISEF>1 Time Dial
Setting for the time multiplier to adjust the operating time of the IEEE/US IDMT curves.
ISEF>1 IDG Time
Setting for the IDG curve used to set the minimum operating time at high levels of fault current.
ISEF>1 Reset Chr
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
ISEF>1 tRESET
Setting to determine the reset/release time for definite time reset characteristic.
ISEF>2 Function
Setting for the tripping characteristic for the second stage sensitive earth fault element.
ISEF>2 Direction
This setting determines the direction of measurement for the second stage sensitive earth fault element.
ISEF>2 Current
Pick-up setting for the second stage sensitive earth fault element.
ISEF>2 IDG Is
This setting is set as a multiple of ISEF> setting for the IDG curve (Scandinavian) and determines the actual relay current threshold at which
the element starts.
ISEF>2 Delay
Setting for the time delay for the second stage definite time element.
ISEF>2 TMS
Setting for the time multiplier to adjust the operating time of the IEC IDMT characteristic.
ISEF>2 Time Dial
Setting for the time multiplier to adjust the operating time of the IEEE/US IDMT curves.
ISEF>2 IDG Time
Setting for the IDG curve used to set the minimum operating time at high levels of fault current.
ISEF>2 Reset Chr
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
ISEF>2 tRESET
Setting to determine the reset/release time for definite time reset characteristic.
ISEF>3 Status
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
3A
33
1
3A
34
1.2
3A
36
DT
3A
37
0
3A
3A
Disabled
3A
3B
Non-Directional
3A
3E
0.05
3A
3F
1.5
3A
41
1
3A
42
1
3A
43
1
3A
44
1.2
3A
46
DT
3A
47
0
3A
49
Disabled
DESCRIPTION
From 0.01 to 100 in steps of 0.01
[Courier Number (decimal)]
From 1 to 2 in steps of 0.01
[Courier Number (time-seconds)]
DT
Inverse
[Indexed String]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
IDG
[Indexed String]
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
From 0.005*I3 to 0.1*I3 in steps of 0.00025*I3
[Courier Number (current)]
From 1 to 4 in steps of 0.1
[Courier Number (decimal)]
From 0 to 200 in steps of 0.01
[Courier Number (time-seconds)]
From 0.025 to 1.2 in steps of 0.005
[Courier Number (decimal)]
From 0.01 to 100 in steps of 0.01
[Courier Number (decimal)]
From 1 to 2 in steps of 0.01
[Courier Number (time-seconds)]
DT
Inverse
[Indexed String]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
Appendix B -Settings and Signals