MENU TEXT
remain 'high' as long as key is pressed.
Fn Key 9 Label
Allows the text of the function key to be changed to something more suitable for the application.
Fn Key 10
Setting to activate function key. The 'Lock' setting allows a function key output that is set to toggle mode to be locked in its current active
position.
Fn Key 10 Mode
Sets the function key in toggle or normal mode. In 'Toggle' mode, a single key press will set/latch the function key output as 'high' or 'low' in
programmable scheme logic. This feature can be used to enable/disable relay functions. In the 'Normal' mode the function key output will
remain 'high' as long as key is pressed.
Fn Key 10 Label
Allows the text of the function key to be changed to something more suitable for the application.
IEC 61850-9.2LE
This column contains all the configure/setting measurement parameters relative to IEC 61850-9-2LE.
Physical Link
AntiAlias Filter
Synchro Alarm
SV Test Mode
This setting is used for processing Sampled Value frames with an IEC 61850 Test mode flag. This setting is common to all SV Logical Nodes
configured in the IED.
Disabled: all channel data frames received with an IEC 61850 Test flag are treated as invalid. The IED blocks relevant protection functions
Enabled: all channel data frames received with an IEC 61850 Test flag are treated as good so all protection functions remain active.
Note: The cell '9.2 Mode' used in software prior to IEC 61850 edition 2 has been renamed as 'SV Test Mode'
Merge Unit Delay
VT Switch Mode
LN Count
LN1 Name
LN2 Name
LN3 Name
LN4 Name
LN5 Name
LN6 Name
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
17
1C
Function Key 1
17
1D
Unlocked
17
1E
Normal
17
1F
Function Key 1
18
00
18
01
Fibre Optic
18
02
Enabled
18
03
Local 1PPS
18
04
Disabled
18
05
1
18
06
Disabled
18
11
1
18
12
MiCOM Logical Node 1
18
13
MiCOM Logical Node 2
18
14
MiCOM Logical Node 3
18
15
MiCOM Logical Node 4
18
16
MiCOM Logical Node 5
18
17
MiCOM Logical Node 6
DESCRIPTION
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
Disabled
Unlocked (Enabled)
Locked
[Indexed String]
Normal
Toggled
[Indexed String]
From 32 to 163 in steps of 1
[ASCII Text (16 chars)]
0 or 1
[Indexed String]
Disabled
Enabled
[Indexed String]
From 0 to 2 in steps of 1
[Indexed String]
0 or 1
[Indexed String]
From 0 to 3 in steps of 0.25
[Numeric(time-ms)]
0 or 1
[Indexed String]
From 1 to 8 in steps of 1
[Integers]
Appendix B -Settings and Signals