GE MiCOM P40 Technical Manual page 876

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

Appendix B -Settings and Signals
MENU TEXT
When Enabled, CB Fail timers will be reset by drop off of a weak infeed trip condition, providing that WI trip logic is activated.
UNDER CURRENT
I< Current Set
Setting that determines the circuit breaker fail timer reset current for overcurrent based protection circuit breaker fail initiation. This setting
is also used in the pole dead logic to determine the status of the pole (dead or live).
ISEF< Current
Setting that determines the circuit breaker fail timer reset current for Sensitive earth fault (SEF) protection circuit breaker fail initiation.
PoleDead Voltage
V<
Under voltage level detector for pole dead detection
GROUP 1: SUPERVISION
This column contains settings for Voltage and Current Supervision
VTS Mode
Setting that determines the method to be used to declare VT failure.
VTS Status
This setting determines whether the following operations will occur upon detection of VTS.
• VTS set to provide alarm indication only.
• Optional blocking of voltage dependent protection elements.
• Optional conversion of directional overcurrent elements to non-directional protection
(available when set to blocking mode only). These settings are found in the function links cell of the relevant protection element columns in
the menu.
VTS Reset Mode
The VTS block will be latched after a user settable time delay 'VTS Time Delay'. Once the signal has latched then two methods of resetting
are available. The first is manually via the front panel interface (or remote communications) and secondly, when in 'Auto' mode, provided the
VTS condition has been removed and the 3 phase voltages have been restored above the phase level detector settings for more than 240 ms.
VTS Time Delay
Setting that determines the operating time-delay of the element upon detection of a voltage supervision condition.
VTS I> Inhibit
The setting is used to override a voltage supervision block in the event of a phase fault occurring on the system that could trigger the
voltage supervision logic.
VTS I2> Inhibit
The setting is used to override a voltage supervision block in the event of a fault occurring on the system with negative sequence current
above this setting which could trigger the voltage supervision logic.
Inrush Detection
This setting is to enable/disable the Inrush Detection used for the Distance protection.
I>2nd Harmonic
If the level of second harmonic in any phase current or neutral current exceeds the setting, inrush conditions will be recognized by changing
the status of four DDB signals from low to high in the Programmable Scheme Logic (PSL). The user then has a choice to use them further in
the PSL in accordance with the application.
WI Inhibit
B130
COL
ROW
DEFAULT SETTING
45
0A
45
0B
0.05
45
0D
0.02
45
0E
45
10
38.1
46
00
46
01
Measured + MCB
46
02
Blocking
46
03
Auto
46
04
5
46
05
10
46
06
0.05
46
0E
Disabled
46
0F
20
46
11
Enabled
DESCRIPTION
[Indexed String]
From 0.02*I1 to 3.2*I1 in steps of 0.01*I1
[Courier Number (current)]
From 0.001*I3 to 0.8*I3 in steps of 0.0005*I3
[Courier Number (current)]
From 10*V1 to 40*V1 in steps of 0.1*V1
[Courier Number (voltage)]
Measured + MCB
Measured Only
MCB Only
[Indexed String]
Disabled
Blocking
Indication
[Indexed String]
Manual
Auto
[Indexed String]
From 1 to 10 in steps of 0.1
[Courier Number (time-seconds)]
From 0.08*I1 to 32*I1 in steps of 0.01*I1
[Courier Number (current)]
From 0.05*I1 to 0.5*I1 in steps of 0.01*I1
[Courier Number (current)]
Disabled
Enabled
[Indexed String]
From 10 to 100 in steps of 5
[Courier Number (percentage)]
Disabled
AVAILABLE OPTIONS
P446SV-TM-EN-1
P446SV

Advertisement

Table of Contents
loading

Table of Contents