P446SV
Signal Name
TARA
CB1-pole / 3-pole trip (13)
TARAny
CB1-pole / 3-pole trip (13)
TARB
CB1-pole / 3-pole trip (13)
TARC
CB1-pole / 3-pole trip (13)
TMEM1Ph
CB1-pole / 3-pole trip (13)
TMEM2/3Ph
CB1-pole / 3-pole trip (13)
TMEM3Ph
CB1-pole / 3-pole trip (13)
TMemAny
CB1-pole / 3-pole trip (13)
4.3

AUTORECLOSE DDB SIGNALS

The following table lists all the DDB signals used in the CB control and Autoreclose logic system:
DDB Signal Name
DDB Signal Number
1P DTime
1554
1P Follower Time
1446
1P Reclaim TComp
1568
1P Reclaim Time
1567
1PF TComp
1561
2/3 Ph Fault
527
3 Ph Fault
528
3P Dead Time IP
853
3P DTime1
1556
3P DTime2
1557
3P DTime3
1558
3P DTime4
1559
3P Follower Time
1447
3P Reclaim TComp
1570
3P Reclaim Time
1569
3PF TComp
1562
Any Trip
522
AR CB1 No C/S
308
AR CB1 Unhealthy
307
P446SV-TM-EN-1
Source
CB Trip Time Monitor (53)
Force 3-phase Trip (10)
CB1-pole / 3-pole trip (13)
Evolving Fault (20)
CB Trip Time Monitor (53)
CB Trip Time Monitor (53)
1-phase AR Cycle Selection (19)
CB1 AR In Progress (16)
Autoreclose Lockout (55)
CB Trip Time Monitor (53)
Autoreclose Lockout (55)
CB1 AR In Progress (16)
Evolving Fault (20)
3-phase AR cycle selection (21)
Source Module (Module Number)
1-phase AR Dead Time (24)
Follower 1-phase CB AR Time (28)
Reclaim Time (35)
Reclaim Time (35)
Follower 1-phase CB AR Time (28)
CB Trip Conversion (63)
CB Trip Conversion (63)
3-phase AR Dead Time (25)
3-phase AR Dead Time (25)
3-phase AR Dead Time (25)
3-phase AR Dead Time (25)
3-phase AR Dead Time (25)
Follower 3-phase CB AR Time (29)
Reclaim Time (35)
Reclaim Time (35)
Follower 3-phase CB AR Time (29)
CB Trip Conversion (63)
CB Healthy and System Check Timers (39)
CB Healthy and System Check Timers (39)
Destination
An A-phase trip has initiated Autoreclose
Any trip has initiated Autoreclose
A B-phase trip has initiated Autoreclose
A C-phase trip has initiated Autoreclose
Signal to remember that Autoreclose was
initiated by a single-phase fault
Signal to remember that Autoreclose was
initiated by a 2-phase fault or a 3-phase
fault
Signal to remember that Autoreclose was
initiated by a 3-phase fault
Signal to remember that Autoreclose was
initiated by an AnyTrip
Sequence Counter (18)
Evolving Fault (20)
Successful AR Signals (36)
Reclaim Time (35)
Follower 1-phase CB AR Time (28)
Successful AR Signals (36)
Reclaim Time (35)
Follower 1-phase CB AR Time (29)
AR Initiation (11)
CB1 Autoclose (32)
CB2 Autoclose (33)
CB Control (43)
CB2 Control (44)
Autoreclose Lockout (55)
Force 3-phase Trip (10)
Autoreclose Lockout (55)
Leader Follower Logic (7)