Commissioning with the BOP-2
You can alter parameter values via the BOP-2. To set parameters on this panel,
you must remove the SDP and attach the BOP-2 (see
Appendix A).
The BOP-2 features a five-digit, seven-segment display
for showing parameter numbers and values, alarm and
fault messages and setpoints and actual values.
Parameter sets cannot be saved via the BOP-2.
Table 3-2 shows the factory default settings for operation
via the BOP-2.
NOTICE
The BOP-2 motor control functions are disabled by default. To control the
motor via the BOP-2, parameter P0700 should be set to 1 and P1000 set to 1.
The BOP-2 can be fitted to and removed from the inverter whilst power is
applied.
If the BOP-2 has been set as the I/O control (P0700 = 1), the drive will stop if
the BOP-2 is removed.
Table 3-2
Default settings for operation using the BOP-2
Parameter
Meaning
P0100
Operating Mode Europe/US
P0307
Power (rated motor)
P0310
Motor frequency rating
P0311
Motor speed rating
P1082
Maximum Motor Frequency
ATTENTION
MICROMASTER 430 can only be operated using a BOP-2 bedient werden.
If a BOP or AOP is used, the following is shown on the display
Default Europe (North America)
50 Hz, kW (60 Hz, hp)
Dimension (kW (Hp)) depending on setting of P0100.
[Value depending on variant.]
50 Hz (60 Hz)
1395 (1680) rpm [depending on variant]
50 Hz (60 Hz)
MICROMASTER 430
.
Operating Instructions
6SE6400-5AC00-0BP0
info@eltra-trade.com
+421 552 601 099

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents