Quick Commissioning

4.1

Commissioning with BOP

Motor parameters detailed below are already set for the respective Siemens
motor at the factory. In order to change parameter settings, use either a
BOP/AOP or a Commissioning Tool (e.g., Drive Monitor).
The parameter sequence below ensures optimized and efficient operation of
the inverter. Note that P0010 must be set to 1 to allow this procedure to be
performed.
When fitted, the jumpers override the parameter settings.
P0010
Start Quick
Commissioning
0 = Ready to Run
1 = Quick Commissioning
30 = Factory Setting
Please note that P0010 must always be
set back to '0' before operating the motor.
However if P3900 = 1 is set after
commissioning this is done automatically.
P0100
Operation for Europe /
N. America
0 =
Power in kW; ƒ default 50 Hz
1 =
Power in hp; ƒ default 60 Hz
2 =
Power in kW; ƒ default 60 Hz
Note: settings 0 & 1 can be changed using
Jumper 60 Hz.
P0304
*Rated Motor Voltage
10 – 2000 V
Nominal motor voltage (V) from rating plate.
Set in factory for respective motor
P0305
*Rated Motor Current
0 – 2 x inverter rated current (A)
Nominal motor current (A) from rating plate.
Set in factory for respective motor.
P0307
*Rated Motor Power
0 – 2000 kW
Nominal motor power (kW) from rating
plate. If P0100 = 1, values will be in hp.
Set in factory for respective motor
P0310
*Rated Motor
Frequency
12 – 650Hz
Nominal motor frequency (Hz) from rating
plate. Set in factory for respective motor.
P0311
*Rated Motor Speed
0 – 40000 1/min
Nominal motor speed (rpm) from rating
plate. Set in factory for respective motor
Table Footnotes
§ Denotes parameters that contain detailed lists of possible settings for use in specific
applications. Refer to the Operating Instructions and Operating Instructions on the CD.
Motor related parameters – please refer to motor rating plate drawing.
14
Getting Started Guide – March 2002
A5E00157510A
Тел.: 8 (0214) 444395, 443688, 442155, (029) 6171554
P0700
Selection of Command
Source
(On / off / reverse)
1 =
Basic Operator Panel
2 =
Terminal/Digital Inputs (Default).
P1000
Selection of Frequency
Setpoint
0 =
No frequency setpoint
1 =
BOP frequency control
27 = Setpoint Addition: Analogue Setpoint
& Control Potentiometer (Default).
P1080
Min. Motor Frequency
Sets minimum motor frequency (0-650Hz)
at which the motor will run irrespective of
the frequency setpoint. The value set here
is valid for both clockwise and anti-
clockwise rotation.
P1082
Max. Motor Frequency
Sets maximum motor frequency (0-650Hz)
at which the motor will run at irrespective of
the frequency setpoint. The value set here
is valid for both clockwise and anti-
clockwise rotation.
P1120
Ramp-Up Time
0 – 650 s
Time taken for the motor to accelerate from
standstill up to maximum motor frequency.
P1121
Ramp-Down Time
0 – 650s
Time taken for motor to decelerate from
maximum motor frequency down to
standstill.
P3900
End Quick
Commissioning
0 =
No Quick Commissioning without
motor calculation or factory reset.
1 =
Perform Quick Commissioning with
factory reset of all other parameters.
(Recommended)
§
§