Technical specifications
Line supply characteristics
Voltage range
Overvoltage category
Permissible supply
configuration
Supply environment
Environmental conditions
Surrounding air
temperature
Storage temperature
Protection class
Maximum humidity level
Shock and vibration
Operating altitude
Environmental classes
* For more information, refer to the SINAMICS V20 Inverter Operating Instructions.
** Note that only unfiltered inverters can be operated on IT power system.
Getting Started
A5E31842771, 02/2013
Three phase AC 400 V inverters
380 V to 480 V AC (tolerance: -15 % to +10
%)
47 Hz to 63 Hz
Current derating exists at the input voltages
/ switching frequencies higher than 400 V /
4kHz. *
EN 60664-1 Category III
TN, TT, IT **, TT earthed line
Second environment (private power network) *
0 °C to 40 °C: without derating
40 °C to 60 °C: with derating *
- 40 °C to + 70 °C
IP 20
95% (non-condensing)
Long-term storage in the transport packaging according to EN 60721-3-1 Class 1M2
Transport in the transport packaging according to EN 60721-3-2 Class 2M3
Vibration during operation according to EN 60721-3-3 Class 3M2
Up to 4000 m above sea level
1000 m to 4000 m: output current derating *
2000 m to 4000 m: input voltage derating *
Pollution class: 3S2
Gas class: 3C2 (SO
, H
2
2
Climate class: 3K3
Single phase AC 230 V inverters
200 V to 240 V AC (tolerance: -10 % to +10 %)
47 Hz to 63 Hz
Current derating exists at the input voltages /
switching frequencies higher than 230 V / 8kHz.
*
TN, TT
S)