2.3

Technical specifications

Three phase AC 400 V inverters
Line supply characteristics
Voltage range
380 V to 480 V AC (tolerance: -15 % to +10 %)
47 Hz to 63 Hz
Current derating exists at the input voltages /
switching frequencies higher than 400 V / 4kHz.
Overvoltage catego-
EN 60664-1 Category III
ry
Permissible supply
TN, TT, IT: FSA to FSE (unfiltered); FSE (fil-
configuration
tered)
TN, TT with grounded neutral: FSA to FSE
Supply environment
Second environment (private power network)
Overload current
Rated power 0.12 kW to 15 kW
Rated power 18.5 kW (HO)/22 kW (HO)
Rated power 22 kW (LO)/30 kW (LO)
Environmental conditions
Surrounding air
- 10 °C to 40 °C: without derating
temperature
40 °C to 60 °C: with derating (UL/cUL-compliant: 40 °C to 50 °C, with derating)
Storage temperature - 40 °C to + 70 °C
Protection class
IP 20
Maximum humidity
95% (non-condensing)
level
Shock and vibration
Long-term storage in the transport packaging according to EN 60721-3-1 Class 1M2
Transport in the transport packaging according to EN 60721-3-2 Class 2M3
Vibration during operation according to EN 60721-3-3 Class 3M2
Operating altitude
Up to 4000 m above sea level
1000 m to 4000 m: output current derating
2000 m to 4000 m: input voltage derating
Environmental clas-
Pollution degree: 2
ses
Solid particles: class 3S2
Chemical gases: class 3C2 (SO
Climate class: 3K3
For more information about current deratings, see the SINAMICS V20 Inverter Operating Instructions.
1)
When the input voltage is below the rated value, current deratings are permissible and therefore the voltage-dependent
2)
speed and/or torque may be reduced.
To operate FSE (filtered) on IT power supply, make sure you remove the screw for the EMC filter.
3)
14
1)
3)
Single phase AC 230 V inverters
200 V to 240 V AC (tolerance: -15 % to +10 %)
2)
47 Hz to 63 Hz
Current derating exists at the input voltages /
switching frequencies higher than 230 V / 8kHz.
TN, TT: FSAA to FSC (unfiltered)
TN, TT with grounded neutral: FSAA to FSC
IT: FSAA/FSAB (unfiltered)
First environment (public power network)
150% rated for 60 seconds
110% rated for 60 seconds
, H
S)
2
2
2)
SINAMICS V20 Inverter
A5E37281078-003, 05/2016

Hide quick links: