Section 4 Initial Setup

4.4 K3HB-S Initial Setup Example (K3HB-SSD)

● Note ●
Do not change the order of step
C.
When input type A is set, the
scaling value and decimal point
position will be initialized
automatically.
4-8
The initial setup is explained in the following example.
Settings Example
In the following setting example, 1 to 5-V input is scaled to the range
0.000 to 1.000.
• If the measurement value goes above 0.700, comparative output
H turns ON.
• If the measurement value goes below 0.500, comparative output L
turns ON.
Display value
1.000
Input
0.000
value
1.000 V 5.000 V
Initial Setup Flow
To change the setting, press the S [SHIFT] Key once. (The setting
that can be changed will start flashing.) Change the set value by
pressing the S [SHIFT] Key and U [UP] Key.
A Check the wiring and turn the power ON. (Connect the sensor to
input A.)
• The input type is factory-set to 4 to 20-mA input. When the power
is turned ON, the display may flash "
range). This simply indicates, however, that the input is outside
the range 4 to 20 mA and does not indicate a product failure.
B Set the calculation to 0.
1. Move to the initial setting level by pressing the L [LEVEL] Key for at least
3 s with the PV displayed (RUN level).
2. Set "cal" to "0" and press the
C Set input type A to 1 to 5 V.
• Set "in-ta" to "1-5" and press the M [MODE] Key.
D Set the scaling value.
1. Set scaling input value A1 "inp. a 1" to "1. 000" and press the
Key.
2. Set scaling display value A1 "dsp. a 1" to "0" and press the
3. Set scaling input value A2 "inp. a2" to "5 000" and press the
Key.
4. Set scaling display value A2 "dsp. a2" to "1000" and press the
Key.
E Set the decimal point position.
1. Set the parameter "dp" to ",,. ,,," and press the M [MODE] Key.
Measurement
value
0.700
0.500
Comparative output H
Comparative output L
a. err
" (outside the input
M
[MODE] Key.
M
M
[MODE]
[MODE] Key.
M
[MODE]
M
[MODE]