Omron K3HB-H User Manual page 46

Digital indicators
Hide thumbs Also See for K3HB-H:
Table of Contents

Advertisement

RUN Level
Initial Setting Level (
• Comparative set value H is 50.00 A and comparative set value L is
40.00 A.
Comparative set value H
50.00 A
40.00 A
Comparative set value L
Output H
Output PASS
Output L
Parameter
Comparative
set value H
Comparative
set value L
✽ Check on the status displays.
0)
The Setting Level Protect setting must be set to 0 (SET.PT = 0) to
L
enable moving to the advanced function setting level.
Parameter
Input type A
Scaling input
value A1
Scaling display
value A1
Scaling input
value A2
Scaling display
value A2
Decimal point
position
Comparative
output pattern
Move to
advanced
function
setting level
3.2 Monitoring Motor Load Current
Level output
Characters Set value
50. 00
Control example for the
following settings:
Comparative output 1:
40. 00
50.00 A
Comparative output 2:
40.00 A
Characters Set value
in-ta
a aa
inp. a 1
0. 000
dsp. a 1
0
75.00 A
inp. a2
5. 000
dsp. a2
7500
0.00 A
dp
,,,. ,,
out-p
level
Level output
amov
-0169
Move to advanced
function setting level to
set the startup
compensation timer
Display
High
Low
ON
OFF
Remarks
Remarks
Display value: CT primary current
K3HB-XAA
input
0.000 A
5.000 A
3-7