Advertisement

5.23 No Output before PASS Range

f
stdby
L
(STDBY)
Comparative set value HH/H
Comparative set value LL/L
The standby sequence function can be used to prevent outputs from
turning ON for unstable inputs after the power is turned ON. All outputs
will remain OFF until the measurement value reaches the PASS value.
Output PASS
Output LL/L
All outputs will remain OFF after power is turned ON
until the measurement value reaches the PASS value.
Parameter
Standby sequence
stdby
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
0" is displayed on the level/bank
• "
L
display to indicate the initial setting
level.
B Press the M [MODE] Key several times
to change the PV display to "amov."
• This parameter is not displayed for
the initial status due to setting level
protect.
Refer to "Limiting Key Operations"
(P.5-102) for information on removing
setting level protect.
C Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
5.23 No Output before PASS Range
Advanced function setting level
X
Measurement value
Set value
Meaning of set value
on
Disabled
off
Enabled
L
3 s min.
M
S
V
S
H
ON
OFF
0
L
0."
Displays "
L
amov
0
L
0
amov
0
L
00000
5-61