Section 3 Basic Application Methods
RUN Level
Initial Setting Level (
Input Adjustment Level
1)
(
L
3-4
Parameter
Characters
Comparative
set value HH
Comparative
set value H
Comparative
set value L
Comparative
set value LL
✽ Check on the status displays.
0)
L
Parameter
Input type A
Scaling input
value A1
Scaling display
value A1
Scaling input
value A2
Scaling display
value A2
Decimal point
position
Comparative
output pattern
Parameter
Timing hold
Zero-limit
Zero-limit value
Averaging type
Averaging
times
Set
value
3400
Control example for the following
3200
settings:
Full tank alarm set: 3,400 mm
Upper limit alarm: 3,200 mm
800
Lower limit alarm: 800 mm
Dry tank alarm: 400 mm
400
Characters Set value
in-ta
d ad
inp. a 1
4. 00
dsp. a 1
3500
inp. a2
20. 000
3,500 mm
dsp. a2
0
dp
,,,,,
out-p
nomal
Characters Set value
tmg-h
nomal
z-lim
on
lim-p
0
avg-t
move
avg-n
4
Remarks
Remarks
Measurement distance
E4PA-LS400-M1
Output
0 mm
4.00 mA
20.00 mA
Remarks
Normal
Enables the zero-limit
function.
Displays 0 for values
less than zero.
Moving average
4