Setting The Measurement Conditions; Switching To "Fun" Mode; Setting The Number Of Channels To Use (Usech) (Example: 2 Channels) - Omron ZN-CTX21 User Manual

Portable power monitor
Hide thumbs Also See for ZN-CTX21:
Table of Contents

Advertisement

3.5

Setting the Measurement Conditions

Set the measurement conditions for the object to measure. The measurement conditions
include six items: the number of channels to use (USECH), the measurement target circuit
(TYPE), the dedicated CT type (CT), the voltage of the measurement target (VOLT), power
factor (PF) and frequency (FREQ).
Note
Refer to the sections below for details on messages displayed on the display unit and
operational key functions.
Refer to: 2.1 Display Unit, 2.2 Control Unit, and 4.2 Setting (FUN Mode Operation)
(1)

Switching to "FUN" Mode

"FUN" mode should be entered for setting measurement conditions. Press the MODE key
until the "FUN" indicator at the right of the display starts blinking.
RUN Mode
(2)

Setting the Number of Channels to Use (USECH) (Example: 2 Channels)

CLEAR
("FUN" Blinking)
USECH
2CH
USECH
1CH
↑Blinking
USECH
2CH
↑Blinking
USECH
2CH
MODE Key
Twice
Press the ▽or △ key until "USECH" appears at the upper row on
the display.
▽or △ Key
Check if "2CH" is displayed at the lower row. If it is displayed, the
number of channels has been already set to "2", and no other
setting is required.
If the above is not displayed, press the SET/REC/STOP key.
The lower row indication starts blinking.
SET/REC/STOP Key
Press the ▽or △ key to display "2CH" at the lower row.
▽or △ Key
Press the SET/REC/STOP key to apply "2CH" for the number of
channels to use. The blinking at the lower row stops.
SET/REC/STOP Key
Next, proceed to the measurement target circuit type (TYPE) and
dedicated CT type (CT) settings.
FUN Mode
"FUN" Blinking
MODE Key
3-7
3. Check and Preparation
MODE Key
THR Mode

Advertisement

Table of Contents
loading

This manual is also suitable for:

Equo series

Table of Contents