Monitoring Motor Load Current - Omron K3HB-H User Manual

Digital indicators
Hide thumbs Also See for K3HB-H:
Table of Contents

Advertisement

Section 3 Basic Application Methods

3.2 Monitoring Motor Load Current

3-6
Advantages of Using the K3HB-X
• The motor load current can be monitored and the measurement
value and output status held when the motor is tripped. The
K3HB-X will hold this status even if a power interruption occurs.
• A 75:5 current transformer (CT) can be used for motor current
detection.
• Up to 10 A can be input directly using the K3HB-XAA.
• Current can be displayed in amperes (A) up to two digits past the
decimal point (@@.@@ A) on the K3HB-XAA.
• Two-level output detection can be used for the upper limit.
• The startup compensation timer on the K3HB-XAA can be set to
prohibit measurements for a certain amount of time after the
motor startup signal is received to prevent judgments that result in
inadvertent output due to inrush current measured when the
motor starts.
• The startup compensation timer is set to 10 s.
• An output is generated when the H and L values exceed the
comparative output settings. (Uses two-level detection for the
upper limit.)
Power
supply
ON
signal
Magnetic
relay
0 to 50 A AC
CT
75:5
0 to 5 A
Motor
Connections Diagram
K3HB-X
100 to 240 VAC
24 VAC/DC
Process Indicator
K3HB-XAA
Comparative output H
Startup compensation
timer input
Comparative output L
Comparative output 1
(comparative output H)
Comparative output 2
(comparative output L)
Power supply side