Performing Linear Output - Omron K3HB-H User Manual

Digital indicators
Hide thumbs Also See for K3HB-H:
Table of Contents

Advertisement

5.24 Performing Linear Output

s
lset. c
L
(LSET.C)
s
lset. v
L
(LSET.V)
s
lset. h
L
(LSET.H)
s
lset. l
L
(LSET.L)
The linear output function outputs currents or voltages proportional to
measurement values as they change.
Select the type of linear output. Set the maximum and minimum output
measurement values to output the current or voltage for those
measurement values.
Voltage Output
Linear output
5 or 10 V
Line A
0 V
Linear output
Linear output
lower limit
upper limit
Current Output
Linear output
20 mA
Line A
0 mA
Linear output
Linear output
lower limit
upper limit
* Areas marked with an asterisk (*) are input error areas. If the "operation at
input error" parameter is set to "input error," then the output would be like
Line B. Otherwise, the output would be like Line A.
* If operation stops without performing a measurement, then the minimum
value (e.g., 4 mA for the 4 to 20 mA range) is output.
* The value set for the upper limit does not necessarily have to be higher than
the value set for the lower limit. The following is an example of reverse
scaling.
Linear output
20 mA
Line A
Line B
4 mA
Linear output
lower limit
5.24 Performing Linear Output
Linear output
5 V
Line A
1 V
Line B
Measurement
Linear output
value
lower limit
Linear output
20 mA
Line A
4 mA
Line B
Measurement
Linear output
value
lower limit
Measurement
Linear output
value
upper limit
Linear output level
X
V
S
H
Line B
Measurement
Linear output
value
upper limit
Line B
Measurement
Linear output
value
upper limit
5-63

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

K3hb-xK3hb-sK3hb-v

Table of Contents