4.4 K3HB-S Initial Setup Example (K3HB-SSD)
F Set comparative set value H to 0.700 and set comparative set
value L to 0.500.
1. Return to the RUN level by pressing the L [LEVEL] Key for at least 1 s.
(Start operation.)
2. Press the M [MODE] Key repeatedly until the status display shows
and then set the value to "0. 700."
3. Press the M [MODE] Key until the status display shows
the value to "0. 500."
G Start actual operation.
1. Press the M [MODE] Key repeatedly to display the measurement values
and start actual operation.
Clearing Settings
If you become confused while setting the parameters and cannot
continue, all settings can be cleared so that you can start over.
Refer to "5.40 Initializing All Settings" (P.5-100) for information on
clearing all settings.
* Refer to "Section 5 Functions and Operations" for details on setting
parameters.
,
H
, and then set
H
4-9