5.9 Selecting Operations for Input Errors

f
s. err
L
(S.ERR)
The display and operation when the input is exceeding input range can
be selected by setting this parameter.
(Refer to "Input Characteristics" (P.A-6) for input ranges.)
Parameter
Operation at
input error
s.err
Each operation is outlined below.
● Disabled
Display
The display is fixed at the
measurement value that
corresponds to the upper or lower
limit of the input range. (The display
doesn't flash.)
● Overflow
Display
The display is fixed and flashes at
the measurement value that
corresponds to the upper or lower
limit of the input range.
● Input error
Display
Error display flashes*
* The errors are "a.err" or "b.err" for the K3HB-S and "s.err" for the
K3HB-X/V/H.
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
0" is displayed on the level/bank
• "
L
display to indicate the initial setting
level.
5.9 Selecting Operations for Input Errors
Advanced function setting level
Set value
Meaning of set value
off
Disabled
over
Overflow
s.err
Input error
Outputs
Outputs correspond to the
fixed display value.
Outputs
Outputs correspond to the
fixed display value.
Outputs
All outputs are turned OFF.
L
3 s min.
X
V
S
H
0
L
0."
Displays "
L
5-29