5.5 Setting Measurement Operations

1
tmg-h
L
(TMG-H)
Applicable models:
K3HB-@@@
+
K35-1
K35-2
K35-3
K35-4
*
Important
Measurement
range upper limit
Power ON
Measurement
value
RESET
HOLD
The PV display will show "-----" during RESET input (no measurement status).
Remarks
The K3HB has 5 measurement modes, which are set using the
following parameter.
Parameter
Timing hold
tmg-h
Normal
• Measurement are performed continuously and outputs are based
on comparative results.
• TIMING inputs are ignored.
• When the measurement value exceeds the measurement range, a
sensor error will occur and all outputs will turn OFF.
• The measurement value immediately prior to a HOLD input is held
during the HOLD input. Measurements are not performed during
RESET input.
• If RESET and HOLD inputs are competing, the RESET input will
take priority.
Measurement value N
A sensor error occurs and all outputs are turned
OFF if the measurement range is exceeded.
Measuring
Measuring
Sensor error
Selecting operations for input errors
Operation will continue if input error enable is set to OFF (disabled) or
OVER (overflow).
5.5 Setting Measurement Operations
Input adjustment level
Set value
Meaning of set value
nomal
Normal
s-h
Sampling hold
p-h
Peak hold
b-h
Bottom hold
p-p
Peak-to-peak hold
Measurement
No measurement
Measuring
value N
P.5-29
X
V
S
H
5-19