Parameter Setting Procedure
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
0" is displayed on the level/bank
• "
L
display to indicate the initial setting
level.
B Press the M [MODE] Key several times
to change the PV display to "out-p."
C Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed and the
SV display starts to flash.
D Use the U [UP] Key to change the set
value.
E Press the M [MODE] Key to switch to
the next parameter.
• The set value is registered.
F Press the L [LEVEL] Key for at least
1 s to return to RUN level.
Remarks
Preventing output chattering
Delaying output OFF timing
Outputting at set intervals
Reversing output logic
Holding already output comparative outputs
Performing output tests
Allocating other outputs to PASS output
5.15 Changing Comparative Output Patterns
L
3 s min.
M
S
U
M
L
1 s min.
P.5-46
P.5-52
P.5-49
P.5-59
P.5-55
P.5-90
P.5-57
0
L
0."
Displays "
L
out-p
0
L
nomal
out-p
0
L
nomal
out-p
0
L
zone
0
L
123. 4
123. 4
5-45