Section 5 Functions and Operations
5-64
* If the upper and lower limit are set to the same value, then the upper
limit will equals the lower limit plus 1 for linear output.
Parameter
Linear current type
lset.c
Linear voltage type
lset.v
Linear output upper
limit
lset.h
Linear output lower
limit
lset.l
* When a linear output is mounted, the "linear current type" or "linear
voltage type" parameter can be set according to the type of linear
output.
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
0" is displayed on the level/bank
• "
L
display to indicate the initial setting
level.
B Press the L [LEVEL] Key once (less
than 1 s) or several times to move to
the linear output level and display
"1set.c."
5" is displayed on the level/bank
• "
L
display to indicate the linear output
level.
C Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
D Use the U [UP] Key to change the set
value.
E Press the M [MODE] Key to switch to
the next parameter.
• The set value is registered.
F Press the L [LEVEL] Key for at least
1 s to return to RUN level.
Set value
Meaning of set value
0-20
0 to 20 mA
4-20
4 to 20 mA
0-5
0 to 5 V
1-5
1 to 5 V
0-10
0 to 10 V
-19999 to
-19999 to 99999
99999
-19999 to
-19999 to 99999
99999
L
3 s min.
L
S
U
M
L
1 s min.
0
L
0."
Displays "
L
lset. c
s
L
0-20
s."
Displays "
L
lset. c
s
L
0
lset. c
s
L
4-20
lset. h
s
L
99999
123. 4
123. 4