Annunciator Output (Out F) - Mitsubishi MELSEC Q Series Programming Manual

Common instruction 1/2
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

OUT F
5.3.4

Annunciator output (OUT F)

OUT F
OUT F
Setting
Data
D
Function
(1) Operation results up to the OUT instruction are output to the designated annunciator.
(2) The following responses occur when an annunciator (F) is turned ON.
• The "USER"/"ERR." LED goes ON.
• The annunciator numbers which are ON (F numbers) are stored in special registers
(SD64 to SD79).
• The value of SD63 is incremented by 1.
(3) If the value of SD63 is 16 (which happens when 16 annunciators are already ON), even if a
new annunciator is turned ON, its number will not be stored at SD64 to SD79.
(4) The following responses occur when the annunciator is turned OFF by the OUT instruction.
The coil goes OFF, but there are no changes in the status of the "USER" / "ERR." LED and
the contents of the values stored in SD63 to SD79.
Use the RST F
the annunciator which was turned OFF by the OUT F
5-28
Command
: Number of the annunciator to be turned ON (bits)
D
Internal Devices
R, ZR
Bit
Word
(Only F)
instruction to make the "USER"/"ERR." LED go OFF as well as to delete
High
Basic
performance
F35
J
\
U
\G
Bit
Word
––
instruction from SD63 to SD79.