Annunciator Output (Out F) - Mitsubishi MELSEC QS Series Programming Manual

Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

5.3.4

Annunciator output (OUT F)

OUT F
OUT F
Function
(1) Operation results up to the OUT instruction are output to the designated annunciator.
(2) The following responses occur when an annunciator (F) is turned ON.
• The "USER" LED goes ON.
• The annunciator numbers which are ON (F numbers) are stored in special registers
(SD64 to SD79).
• The value of SD63 is incremented by 1.
(3) If the value of SD63 is 16 (which happens when 16 annunciators are already ON), even if a
new annunciator is turned ON, its number will not be stored at SD64 to SD79.
(4) When the annunciator is turned OFF by the OUT instruction, although the coil goes OFF,
status of the "USER" LED and the contents of SD63 to SD79 are not changed.
To turn OFF the "USER" LED or to delete the annunciator, which was turned OFF by the
OUT F
Operation Error
(1) There are no operation errors associated with the OUT F
Remark
Command
: Number of the annunciator to be turned ON (bits)
D
Internal Devices
Set
Data
Bit
Word
D
(Only F)
instruction from SD63 to SD79, use the RST F
1. Refer to the manual below for details of annunciators.
• QSCPU User's Manual (Function Explanation, Program Fundamentals)
2. The number of basic steps for the OUT module F
F35
Constants
Others
––
instruction.
instruction.
instruction is 2.
5.3 Output Instruction
5.3.4 Annunciator output (OUT F)
OUT F
Annunciator number
5
5-25