3.6

Cautions on Programming (Operation Errors)

Operation errors are returned in the following cases when executing basic instructions and
application instructions with CPU module:
• An error listed on the explanatory page for the individual instruction occurred.
• When an intelligent function module device is used, no intelligent function module is installed
at the specified I/O number position.
• When an intelligent function module device is used, the specified buffer memory address does not exist.
• The relevant network does not exist when using a link device.
• When a link device is used, no network module is installed at the specified I/O number position.
• When a multiple CPU shared device is used, a CPU module is not installed at the head I/O
number position of the specified CPU module.
• When a multiple CPU shared device is used, the specified shared memory address does not exist.
• The setting of the device number crosses over the boundary between the internal user device
and the extended data register (D) or extended link register (W).
(Universal model QCPU (excluding Q00UJCPU) and LCPU)
When file register is set but a memory card is not installed or when file register is
not set, writing/reading to/from file register is as follows:
(1) For the High Performance model QCPU, Process CPU, and Redundant CPU
(2) For the Universal model QCPU and LCPU
(1) Device range check
Device range checks for the devices used by basic instructions and application instructions
in CPU module are as indicated below:
(a) Instructions for specified each device, including MOV and DMOV
1) For the Basic Model QCPU, High Performance model QCPU, Process CPU,
*1:
For the assignment order of internal user devices, refer to this Section (c) Character string data.
An error does not occur even when writing/reading to/from file register is
performed. However, "0
H
performed.
The OPERATION ERROR (error code:4101) occurs when writing/reading to/
from file register is performed.
and Redundant CPU
The device range is not checked. In cases where the corresponding device
range is exceeded, data is written to other devices. *
For example, in a case where the data register has been allocated 12k points,
there will be no error even if it exceeds D12287.
DMOV K100 D12287
Device range checks are not conducted also in cases where indexing is being
performed.
In cases where the corresponding device range is exceeded as the result of
performing indexing, data is written to other devices.*
" is stored when reading from file register is
This designates D12287 and D12288 as the
target devices for executing the DMOV instruction.
However, since D12288 does not exist,
data in another device is corrupted.