Reducing Radiated and Radio Frequency Noise
The drive, input lines, and output lines generate radio frequency noise. Use noise filters on input and output sides and install
the drive in a metal enclosure panel to reduce radio frequency noise.
Note:
The cable running between the drive and motor should be as short as possible.
A – Metal enclosure
B – Power supply
C – Noise filter
D – Drive
u

Installing Input Fuses

NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.
Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral
devices if the cause cannot be identified.
Factory Recommended Branch Circuit Protection for UL Compliance
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.
Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral
devices if the cause cannot be identified.
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
Nominal
Drive Model
Output Power
HP
5A0003
5A0004
5A0006
5A0009
7.5
5A0011
10
5A0017
15
5A0022
20
5A0027
25
5A0032
30
5A0041
40
5A0052
50
5A0062
60
5A0077
75
5A0099
100
5A0125
125
5A0145
150
5A0192
200
5A0242
250
<1> Maximum MCCB Rating is 15 A, or 200 % of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
C
B
MCCB
R/L1
S/L2
T/L3
Figure 6.13 Reducing Radio Frequency Noise
Table 6.3 Factory Recommended Drive Branch Circuit Protection
AC Drive Input
Amps
2
3.6
3
5.1
5
8.3
12
16
23
31
38
45
44
54
66
80
108
129
158
228
263
A
E
D
F
U/T1
V/T2
W/T3
E – Noise filter
F – Shielded motor cable
G – Motor
MCCB Rating
Time Delay Fuse
Amps
Rating Amps
<1>
600 V Class
15
6.25
15
8
15
12
20
20
30
25
40
40
60
50
75
60
75
75
75
75
100
90
125
110
150
125
175
175
225
225
300
275
400
350
500
450
6.5 Installing Peripheral Devices
G
M
Table
Bussmann Semi-
Non-time Delay
conductor Fuse
Fuse Rating
<2>
Rating (Fuse
<3>
Amps
Ampere)
10
FWP-50B (50)
15
FWP-50B (50)
20
FWP-60B (60)
35
FWP-60B (60)
45
FWP-70B (70)
60
FWP-100B (100)
90
FWP-100B (100)
110
FWP-125A (125)
125
FWP-125A (125)
125
FWP-175A (175)
150
FWP-175A (175)
175
FWP-250A (250)
225
FWP-250A (250)
300
FWP-250A (250)
350
FWP-350A (350)
450
FWP-350A (350)
600
FWP-600A (600)
700
FWP-600A (600)
6.3.
<4>
6
255

Advertisement

Table of Contents
loading

Table of Contents