Power Specifications
Feature
Input voltage:
Single-phase option
Three-phase option
Frequency:
Maximum power consumption:
Compute rack
Router rack
I/O rack
Hold-up time
Total harmonic distortion
Power cable
Power receptacle:
Compute, router, or I/O rack
(three-phase option)
Compute or router rack
(single-phase option)
I/O rack (single-phase option) (1) 30 A, NEMA L6-30R
Wall breaker size:
Single-phase
Single-phase (Europe)
Three-phase
007-4653-001
Table A-3 lists the power specifications for the server.
Table A-3
Power Specifications
Specification
180 - 254 VAC
180 - 254 VAC (North America/Japan)
or 312 - 440 VAC (international)
North America / Japan
47-63 Hz
9.03 kVA (8.85 kW)
1.63 kVA (1.60 kW)
3.45 kVA (3.38 kW)
20 ms
Less than 10% THD-Rms at full load
8-ft (2.4-m) pluggable drop cord(s)
North America / Japan
(1) 60 A, IEC60309, 4 wire
(1 or 2) 30 A, NEMA L6-30R
30 A
32 A
60 A
Power Specifications
International
47-63 Hz
International
(1) 32 A, IEC60309, 5 wire
(1 or 2) 32 A, IEC60309
(1) 32 A, IEC60309
239
Need help?
Do you have a question about the Origin 3900 and is the answer not in the manual?