Omron SYSMAC CJ Series User Manual page 149

Sysmac cj series cpu unit pulse i/o module
Hide thumbs Also See for SYSMAC CJ Series:
Table of Contents

Advertisement

Name
High-speed
Counter 2 Compar-
ison In-progress
Flag
High-speed
Counter 2 Over-
flow/Underflow
Flag
High-speed
Counter 2 Count
Direction
CJ2M CPU Unit Pulse I/O Module User's Manual
Word/Bit
Function
A320.08
This flag indicates whether a com-
parison operation is being executed
for high-speed counter 2.
OFF: Stopped.
ON: Being executed.
A320.09
This flag indicates when an over-
flow or underflow has occurred in
the high-speed counter 2 PV.
(Used only when the counting mode
is set to Linear Mode.)
OFF: Normal
ON: Overflow or underflow
A320.10
This flag indicates whether high-
speed counter 2 is currently being
incremented or decremented. The
counter PV for the current cycle is
compared with the PV in last cycle
to determine the result.
OFF: Decrementing
ON: Incrementing
7 High-speed Counters
Read/Write
Refresh timing
Read
• Cleared when power is
turned ON.
• Cleared when starting
operation.
• Refreshed when start-
ing/stopping compari-
son.
Read
• Cleared when power is
turned ON.
• Cleared when opera-
tion starts.
• Cleared when the PV is
changed.
• Refreshed when an
overflow or underflow
occurs.
Read
• Setting used for high-
speed counter, valid
during counter opera-
tion.
• Refreshed each cycle
during overseeing pro-
cess.
• Refreshed when
PRV(881) instruction is
executed to read the PV
or status.
7
7-39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cj2m-cpu seriesSysmac cj2m-md21 series