Omron SYSMAC CJ Series User Manual page 219

Sysmac cj series cpu unit pulse i/o module
Hide thumbs Also See for SYSMAC CJ Series:
Table of Contents

Advertisement

Name
Word/Bit
Pulse Output 0
A280.02
Output Amount
Set Flag
Pulse Output 1
A281.02
Output Amount
Set Flag
Pulse Output 2
A326.02
Output Amount
Set Flag
Pulse Output 3
A327.02
Output Amount
Set Flag
Pulse Output 0
A280.03
Output Com-
pleted Flag
Pulse Output 1
A281.03
Output Com-
pleted Flag
Pulse Output 2
A326.03
Output Com-
pleted Flag
Pulse Output 3
A327.03
Output Com-
pleted Flag
Pulse Output 0
A280.04
Output In-
progress Flag
Pulse Output 1
A281.04
Output In-
progress Flag
Pulse Output 2
A326.04
Output In-
progress Flag
Pulse Output 3
A327.04
Output In-
progress Flag
Pulse Output 0
A280.05
No-origin Flag
Pulse Output 1
A281.05
No-origin Flag
Pulse Output 2
A326.05
No-origin Flag
Pulse Output 3
A327.05
No-origin Flag
CJ2M CPU Unit Pulse I/O Module User's Manual
Function
This flag will be ON when the number of output
pulses for pulse output 0 to 3 has been set
with the PULS(886) instruction.
OFF: Not set,
ON: Set
This flag will be ON when the number of output
pulses set with the PULS(886), PLS2(887), or
IFEED(892) instruction has been output
through pulse output 0 to 3.
OFF: Output not completed,
ON: Output completed
This flag will be ON when pulses are being
output from pulse output 0 to 3.
OFF: Stopped,
ON: Outputting
This flag will be ON when the origin has not
been defined for pulse output 0 to 3 and goes
OFF when the origin has been defined.
OFF: Origin established,
ON: Origin not established
8 Pulse Outputs
Read/
Refresh timing
Write
Read
• Cleared when power is
turned ON.
• Cleared when operation is
started or stopped.
• Refreshed when
PULS(886) instruction is
executed.
• Refreshed when pulse
output is stopped.
Read
• Cleared when power is
turned ON.
• Cleared when operation is
started or stopped.
• Refreshed when pulse
output is started or
stopped in Independent
Mode.
Read
• Cleared when power is
turned ON.
• Cleared when operation is
started or stopped.
• Refreshed when start-
ing/stopping pulse output
Read
• Turned ON when power is
turned ON.
• Turned ON when starting
operation.
• Turned ON when the pulse
output is reset.
• Turned ON when an origin
search is started.
• Turned ON when a limit
input is received and clear-
ing is set.
• Turned ON when an over-
flow or underflow occurs.
• Turned OFF when an ori-
gin search is completed.
• Turned OFF when
INI(880) instruction is exe-
cuted to change the PV.
8
8-59

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cj2m-cpu seriesSysmac cj2m-md21 series

Table of Contents